7.1.2 Check gas connection pressure
The gas connection pressure must be within the following ranges:
Natural Gas E/H
17.0 …
20
… 25.0 mbar
Natural Gas LL
20.0 …
25
… 30.0 mbar
Liquid Petroleum Gas P (
P
n 37)
25.0 …
37
… 45.0 mbar
Liquid Petroleum Gas P (
P
n 50)
42.5 …
50
… 57.5 mbar
▶
Open screw on test point Pe the gas pressure switch (see Ch. 7.1.1).
▶
Connect pressure measuring device.
▶
Slowly open isolating valve whilst checking the pressure increase.
Gas connection pressure exceeds 60 mbar pressure:
▶
Immediately close isolating valve.
▶
Do not start plant.
▶
Inform system operator.
Gas connection pressure is insufficient:
▶
Do not start plant.
▶
Inform system operator.
DANGER
Risk of explosion due to leaking gas
Improper work can lead to escaping gas and explosions.
▶
Tightly close screws after working on the test points of the gas combi valve.
Installation and operating instruction
Gas condensing boiler WTC-GB 90-A
7 Commissioning
83266502 • 1/2010-08 • La