Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
9 Servicing
83260202 1/2019-02 La
102-144
Deactivate E-Parameters
Following commissioning, set parameter
E
to
0
.
Press [Enter] and [+] keys simultaneously for approx. 2 seconds.
The parameter level is activated.
Press [+].
Press [Enter] key until parameter
E
is displayed.
Set parameter
E
to
0
.
E
-Parameters are not shown in the setting level.
Press [Enter] key twice.
The combustion manager returns to the operating level.
2. Preset oil side and adjust
Set fuel selection switch to OIL.
Unplug bridging plug No. 7 on combustion manager.
Switch on voltage supply.
The display shows the unprogrammed condition of the combustion manager.
Press [G] and [L/A] simultaneously.
Combustion manager changes to access level.
Press [+].
Combustion manager changes into the setting level for step points.
Determine the operating points for oil operation from the sticker
1
.
Set the burner using these operating points and adjust [ch. 7.2.2].
Brennereinstellungen
Datum:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maß X:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
mm
Gaseinstelldruck bei Großlast:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
mbar
Voreinstellung Luftklappe bei Großlast P9:
. . . . . . . . . . . . . . . . . . .
°
Techniker:
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Gasbetrieb
Punkt G L/A
P0
P1
P2
P3
P4
P5
P6
P7
P8
P9
bo
bu
Ölbetrieb
Punkt L/A
P0
P1
P2
P3
P9
1