Installation and operating instruction
Dual fuel burner WGL30/1-C ZM
9 Servicing
83260202 1/2019-02 La
100-144
9.19 Replacing the combustion manager
Observe notes on servicing [ch. 9.1].
Unplug all plugs.
Undo screws
1
.
Push combustion manager upwards and replace.
1
Connect all plugs again.
1. Preset gas side and adjust
Set fuel selection switch to GAS.
Unplug bridging plug No. 7 on combustion manager.
Switch on voltage supply.
The unprogrammed condition of the combustion manager is indicated by a flash-
ing display.
The burner goes to lockout.
Press [ENTER].
Burner has been reset.
Combustion manager drives to Standby.
Activate parameter level [ch. 6.2.3].
Set parameter
7
and
8
to
1
.
Press [G] and [L/A] simultaneously.
Combustion manager changes to access level.