background image

KNX ENO 634 

WEINZIERL ENGINEERING GmbH 

EN 

2013-08-14 

Page 9/11 

Controller 

 

Fig. 23: Controller 

 
Two-point float 
 

Comm.-Object 

Type KNX 

Size 

Channel…: Controller On/Off 

1.001 

1 Bit 

Channel…: Setpoint (absolute) 

9.001 

2 Byte 

Channel…: Setpoint (relative) 

9.002 

2 Byte 

Channel…: Value actual 

9.001 

2 Byte 

Channel…: Switch 

1.001 

1 Bit 

 
Continuously float 
It is a continuous temperature controller with night-, 
presence and window-/door-function. 
 

Comm.-Object 

Type KNX 

Size 

Channel…: Controller On/Off 

1.001 

1 Bit 

Channel…: Setpoint (absolute) 

9.001 

2 Byte 

Channel…: Setpoint (relative) 

9.002 

2 Byte 

Channel… Temperature actual 
value 

9.001 

2 Byte 

Channel…: Night 

1.001 

1 Bit 

Channel…: Presence 

1.018 

1 Bit 

Channel…: Window open 

1.019 

1 Bit 

Channel…: Control variable 

5.001 

1 Byte 

 
Heat demand requirements 
The maximum value of the control inputs from1 to 6 is 
transmitted to the output. Only the highest value is 
passed. The value of the datapoint “Demand” will be 
set to “1”, when the maximal value is greater than ze-
ro. 
 

Comm.-Object 

Type KNX 

Size 

Channel…: Control value 1 

5.001 

1 Byte 

Channel…: Control value 2 

5.001 

1 Byte 

Channel…: Control value 3 

5.001 

1 Byte 

Channel…: Control value 4 

5.001 

1 Byte 

Channel…: Control value 5 

5.001 

1 Byte 

Channel…: Control value 6 

5.001 

1 Byte 

Channel…: Demand 

1.001 

1 Bit 

Channel…: Max value 

5.001 

1 Byte 

 
Lighting control 
Several functions can be realized: 

Full-automatic control 

A  typical  application  for  the  fully  automatic  control  is 
the lighting of a corridor. 
The  light  is  turned  on  in  presence  when  the  current 
brightness  value  is  below  the  threshold.  By  manual 
operation,  the  light  can  be  switched  on  or  off  for  a 
specific time. 

Semi-automatic control 

The semiautomatic mode allows the user or residents 
to  turn  the  lights  on  and  off  manually.  The  semi-
automatic  only  intervenes  when  the  light  was  ‘forgot-
ten’. A typical application is an office room with sever-
al desks. 
The  light  will  not  be  switched  on  automatically.  The 
semi-automatic switches the light off when the current 
brightness value is above the threshold or when for a 
defined time presence is no longer detected. 

Simple control 

The  simple  control  only  evaluates  the  brightness  and 
can be used, for example, for a store window. 
The  light  turns  on  if  it  is  too  dark,  and  automatically 
turns off when the brightness limit is reached. 
 

Comm.-Object 

Type KNX 

Size 

Channel…: Controller on/off 

1.001 

1 Bit 

Channel…: Light on/off 

1.001 

1 Bit 

Channel…: Presence 

1.019 

1 Bit 

Channel…: Light actual value 

9.004 

2 Byte 

Channel…: Switch 

1.001 

1 Bit 

Channel…: Dimm value 

5.001 

1 Byte 

 
 

Logic element 

 

Fig. 24: Logic element 

 
AND-, OR-, XOR-, NAND-, NOR-, XNOR-Gate 
Two different logic functions can be selected inde-
pendently for Type A or Type B. 
 

Comm.-Object 

Type KNX 

Size 

Channel…: Gate input A1 

1.001 

1 Bit 

Channel…: Gate input A2 

1.001 

1 Bit 

Channel…: Gate output A 

1.001 

1 Bit 

Channel…: Gate input B1 

1.001 

1 Bit 

Channel…: Gate input B2 

1.001 

1 Bit 

Channel…: Gate output B 

1.001 

1 Bit 

 

Summary of Contents for KNX ENO 634

Page 1: ... gateway supports logical and control functions and in cludes radio repeater functionality The KNX ENO 634 is divided in 32 channels Each channel can be as signed to one of the following functions Link from EnOcean sensor to KNX Switch functions Switching Dimming Shutter Scene Window handles Window contacts Access card switches Press switches Temperature sensors Humidity sensors Light sensors Pres...

Page 2: ...er Deleting links for RF sensors and Deleting links for RF actua tors Key press T1 short Exit Leave channel linking mode Key press T2 long Add Start linking mode Refer to chapter Linking mode for sensors and Linking mode for actuators Key press T2 short Active Activate or change the channels 1 32 Key press T3 Activate KNX Prog mode The KNX device can now receive a new individual ad dress Refer to ...

Page 3: ...handles RPS after 3 tel must be selected The sensor has to send three telegrams within 10 se conds to be linked The link mode is terminated by a short press of the left key T1 as well as automatically after 5 minutes without operation Quick guide linking mode for RF sensors 1 T2 short press to select the desired channel 2 T2 long press to activate the learning mode Wait for ENO 3 Activate the lear...

Page 4: ...n telegram will be compared to see if it has been assigned to a Channel If so the channel is shown shortly in a matrix on the LCD display De pending on the configured function there will be one or more telegrams sent on the bus The gateway only sends telegrams to the KNX bus when a correspond ing EnOcean telegram has been received If an EnOcean telegram is not assigned to any channel only the sign...

Page 5: ...ush if the actu ator supports this Comm Object Type KNX Size Channel Scene 18 001 1 Biyte Other switches and contacts Fig 8 Other switches and contacts In the submenu Other switches and contacts window contacts window handles key card switches and pressure switches can be integrated For window handle sensors three states can be de tected Window is open tilted or closed When turn ing the handle in ...

Page 6: ...is available as a 2 byte float value Comm Object Type KNX Size Channel Lux 9 004 2 Byte Presence sensors Fig 12 Occupancy sensors In this section presence sensors and motion detectors can be integrated Comm Object Type KNX Size Channel presence 1 018 1 Bit Light Temperature und occupancy sen sors Fig 13 Light Temperature und occupancy sensors Light intensity and temperature are each mapped to a co...

Page 7: ...076 4 Byte Channel Current water l h 9 025 2 Byte Environmental and weather sensors Fig 17 Environmental sensors The following environmental sensor types can be pro grammed Weather station sunlight northern hemi sphere date time and day direction and geographic position Depending on the setting there are different communication objects for each sensor type Weather station Comm Object Type KNX Size...

Page 8: ...le contact input On or off will be sent Comm Object Type KNX Size Channel Window open 1 019 1 Byte HVAC Actuator for valve drive Fig 21 HVAC actuator In this configuration battery operated heating and air actuators can be controlled The temperature values sent by the actuator will be sent to the bus A tele gram is sent when the EnOcean device signals a low battery Battery operated heating and vent...

Page 9: ...automatic control A typical application for the fully automatic control is the lighting of a corridor The light is turned on in presence when the current brightness value is below the threshold By manual operation the light can be switched on or off for a specific time Semi automatic control The semiautomatic mode allows the user or residents to turn the lights on and off manually The semi automat...

Page 10: ...r level corresponding to the config ured condition Is this condition is fulfilled the value 1 will be sent via the output datapoint Comm Object Type KNX Size Channel Trigger value in A D 5 000 1 Byte Channel Trigger binary out A D 1 001 1 Bit Trigger float Up to 2 float triggers can be implemented on one channel The trigger compares the input value with the configured trigger level corresponding t...

Page 11: ...d data is displayed also in hexadecimal cod ing in the second numeric part If a message is sent by the gateway it is displayed in the first position of the line with an S The ID used by the gateway and the transferred data are also shown Fig 27 EnOcean bus monitor KNX bus monitor The KNX bus monitor displays the messages at the object level Therefore only group telegrams are visi ble which address...

Reviews: