background image

 

Start URL 

 

1.

 

E

nter the Webserver IP Address of 

  the target device t

o be connected. 

 

2.

 Enter the Path or URL of the HTML   

file name right after the “/” slash. 
 

3.

 

When resetting HMI or communication   

failure happens, the seconds in which HMI   
attempts the connection again can be set. 
 

Info 

Display HMI information, including   
MicroBrowser version and firmware version. 
 

Click ”Software Update” to update   
MicroBrowser Version. 

 

 

 

 

 

1. 

Insert a SD card into HMI, click   

”Software Update” to start updating. 
 

2. 

Or, after inserting SD card, switch ON   

DIP SW3 and then reboot HMI. 
 
 
 

 

 

 

DIP SW Settings 

 

 

Power 

The HMI can be powered by DC power only, voltage range: 24±20% Volts DC, compatible with 

most controller DC systems. The power conditioning circuitry inside the unit is accomplished by 

a switching power supply. The peak starting current can be as high as 2A.

 

 

Fusing 
Require- 
ments 

If the display does not come on within 5 seconds of power up, remove power. An internal fuse 

will prevent damage if the polarity of the DC power is incorrect. Check wiring for proper 

connections and try to power up again. 

 

High 
Voltage 

An Internal fuse will prevent damage for over voltage condition however it isn

’t guaranteed. DC 

voltage sources should provide proper isolation from main AC power and similar hazards. 

 

Emergency 
Stop 

A Hard-wired EMERGENCY STOP should be fitted in any system using HMI to comply with ICS 

Safety Recommendations. 

 

Supply 
Voltage 
Condition 

Do not power the HMI and inductive DC loads, or input circuitry to the controller, with the same 

power supply. Note: The 24 VDC output from some controllers may not have enough current to 

power the HMI. 

 

Wire 
Routing 

a. Wire lengths should be minimized (Max: 500m shielded, 300m unshielded). 

b. Wires should be run in pairs with a neutral or common paired with a hot or signal line. 

c. If wiring is to be exposed to lightning or surges, use appropriate surge suppression devices. 

d. Keep AC, high energy, and rapidly switching DC wiring separate from signal wires. 

e. Equip ungrounded DC supplies with a resistor and capacitor in parallel to earth ground. 

This provides a path for static and high frequency dissipation. Typical values to use are 1MOhm 

and 4700pF. 

 

 

Hardware 
Considerations 

The system designer should be aware that devices in Controller systems could fail and thereby 

create an unsafe condition. Furthermore, electrical interference in an operator interface can lead 

to equipment start-up, which could result in property damage and/or physical injury to the 

operator. 

If you use any programmable control systems that require an operator, be aware that this 

potential safety hazard exists and take appropriate precautions. Although the specific design 

steps depend on your particular application, the following precautions generally apply to 

installation of solid-state programmable control devices, and conform to the guidelines for 

installation of Controllers recommended in NEMA ICS 3-304 Control Standards.

 

 

Programming 
Considerations 
 

To conform with ICS Safety Recommendations, checks should be placed in the controller to 

ensure that all writable registers that control critical parts of plant or machinery have limit 

checks built into the program, with an out-of-limit safe shut down procedure to ensure safety of 

personnel. 

GME60IWP0_MT605_607_610iWPV1WK_Installaiton_120525 

 

 

 

 

 

DANGER 

CAUTION

NN

 

 

Limited Warranty                                                                                                         

 

This product is limited warranted against defects in design and manufacture. The proven 

defective pro

duct will either be repaired or replaced, at Weintek’s discretion. This warranty 

shall not cover any product which is   

 

(a) Out of warranty period which is 1 year from the date of purchase. 
(b) Damage caused by Force Majeure, accident, negligence, improper installation or misuse.   
(c) Product has been repaired or taken apart by unauthorized technicians.   
(d) Products whose identification markings have been removed or damaged.

 

                                                           

NOTE:   

Make sure that all local and national electrical standards are met when installing 
the unit. Contact your local authorities to determine which codes apply. 

CAUTION 

NOTE: 

Make sure that all local and national electrical standards are met when 

installing the unit. Contact your local authorities to determine which codes apply. 

SW1 

SW2 

SW3 

SW4 

Mode 

ON 

OFF 

OFF 

OFF 

Touch Screen Calibration Mode 

OFF 

ON 

OFF 

OFF 

Hide HMI System Setting Bar 

OFF 

OFF 

ON 

OFF 

Boot Loader Mode 

OFF 

OFF 

OFF 

ON 

MT607iWP/MT610iWP

 Normal 

 

MT605iWP

 Must stay OFF

 

 

OFF 

OFF 

OFF 

OFF

 

MT605iWP

 Normal 

 

MT607iWP/MT610iWP

 Must stay OFF 

 

NOTE:   

Since MT605iWP (4.3

”) does not support 

SD card, to update MicroBrowser version, 

please contact your distributor. 

 

Reviews: