 DVC6200 or DVC2000 Digital Valve 

Controller on 1051 Size 33 and 1052  

Mounting Instructions 

D103447X012

May 2010 

Size 20 and 33 Actuator

 (Window Mount)

 

Use these instructions to mount a Fisher

®

 FIELDVUE

TM

 

DVC6200 or DVC2000 digital valve controller on Fisher 

1051 Size 33 and 1052 Size 20 and 33 actuators. 

 

 

 

Avoid personal injury or property damage from 

sudden release of process pressure or bursting of 

parts. Before performing any installation 

operations: 

 

 

 

Always wear protective clothing, gloves, and 

eyewear.

 

 

Do not remove the actuator from the valve while 

the valve is still pressurized. 

 

 

Disconnect any operating lines providing air 

pressure, electric power, or a control signal to 

the actuator. Be sure the actuator cannot 

suddenly open or close the control valve. 

 

 

Use bypass valves or completely shut off the 

process to isolate the control valve from 

process pressure. Relieve process pressure 

from both sides of the control valve. 

 

 

Vent the pneumatic actuator loading pressure 

and relieve any actuator spring 

precompression. 

 

 

Use lock-out procedures to be sure that the 

above measures stay in effect while you work 

on the equipment. 

 

 

Check with your process or safety engineer for 

any additional measures that must be taken to 

protect against process media. 

 

 

Refer to figure 2 and the parts list for mounting parts 

identification. Refer to the DVC6200 or DVC2000 digital 

valve controller instruction manual for digital valve 

controller parts identification. Refer to the appropriate 

actuator instruction manual for actuator installation, 

operation, maintenance, and parts identification. Figure 

1 shows the arced feedback assembly. 

 

1. Isolate the control valve from the process line 

pressure and release pressure from both sides of the 

valve body. Shut off all pressure lines to the actuator, 

releasing all pressure from actuator.  

Use lock-out procedures to be sure that the above 

measures stay in effect while you work on the 

equipment. 

 

 

2. Remove the cover plate screws and cover plate from 

the actuator, if present. 

 

3. Install the cam (key 1) on to the lever of actuator using 

hex head mach screws (key 2). It will be necessary for 

use of arced feedback mechanism. Consult the 

appropriate actuator instruction manual for proper 

actuator disassembly and reassembly. Ensure that the 

cam is oriented as shown in figure 2. 

 

4. Attach the mounting adaptor (key 3) to the yoke using 

the four hex socket cap screws (key 4).  

 

5. Attach the digital valve controller to the arced 

feedback assembly (key 5) and tighten the hex socket 

cap screws (key 6). 

 

6. Install the arced feedback assembly (key 5), along 

with the digital valve controller, to the mounting adaptor  

(key 3)  using hex socket cap screws (key 7) as shown in 

figure 2. Ensure that the roller of arced feedback 

assembly is centered and resting on the cam surface.  

 

7. Make pneumatic and electrical connections to the 

digital valve controller as described in the digital valve 

controller instruction manual.  

 

8. It may be necessary to fine tune the placement of the 

cam so that the digital valve controllers receives the 

proper feedback. 

 

9. Setup and calibrate the digital valve controller as 

described in the instruction manual or quick start guide.  

 

For additional information concerning mounting, setup, 

calibration, and maintenance of the DVC6200 or 

DVC2000 digital valve controller, refer to the appropriate 

instruction manual.  

 

Note

 

Neither Emerson, Emerson Process 

Management, nor any of their affiliated 

entities assumes responsibility for the 

selection, use or maintenance of any 

product. Responsibility for the selection,  

use, and maintenance of any product  

remains with the purchaser and end user.  

 

 

 

______________________________________________________________________________________________________ 

w

 

Polígono Industrial O Rebullón s/n. 36416 - Mos - España - [email protected]

Servicio de Att. al Cliente

+34 986 288118

Polígono Industrial O Rebullón s/n. 36416 - Mos - España - [email protected]

Servicio de Att. al Cliente

+34 986 288118

Отзывы: