iR-AQ04-VI iR-AM06-VI iR-AI04-VI
11
Analog Output – Soft Start
6.3
Generally, when changing analog output value, the voltage or current output will
change immediately. To gradually increase or decrease output for reducing potential
system impact, an [Output Update Time] parameter can be configured. Adjusting
Output Update Time can get a slew rate where the change of voltage or current from
minimum to maximum value per unit of time is defined, as illustrated in the following
figures.
Time
Analog
Value
Output Update Time
Upper Limit
Lower Limit
m(
Slope)
Time
Analog Value
m
m
m
Parameter
Description
Default
Output Update Time
The time unit is 10ms. By default this parameter is set to 0
(disabled). The maximum allowable setting is 3200 (32
seconds)
0