iR-AQ04-VI iR-AM06-VI iR-AI04-VI
9
6.
Analog I/O Features
Feature List
6.1
No.
Feature
Descriptions
1
User-Defined Conversion Rate
2
Analog Output – Soft Start
3
Diagnose
Analog Output
Voltage Short Circuit Detection & Protection
Voltage Open Circuit Detection & Protection
4
Analog Input
Disconnection Detection (1-5v / 4-20mA)
5
Analog Input – Fast Conversion Mode
6
Analog Input – Digital Filter
User-Defined Conversion Rate
6.2
iR-Axxx-VI Series models support built-in digital-to-analog conversion with
user-defined range. Available ranges are:
±
10V,
±
5v, 1-5v,
±
20m, 4-20mA.
Example: When the defined mode is
±
10V, the default scale range is
±
32000.
Converting analog value 10v will get the upper limit of the range, which is 32000.
Converting analog value -10v will get the lower limit of the range, which is -32000.
10v
Upper Limit
Lower Limit
-10v
5v
-5v
1v
5v
-20mA
20mA
4mA
20mA
Mode:
±10v
±5v
1-5v
±20mA
4-20mA