Weil-McLain Ultra 105 Quick Start Manual Download Page 5

INSTALLING THE 

PRIMARY/SECONDARY TEES

The near-boiler piping must be 
primary/secondary as shown above 
and left, with the boiler loop piping 
entering the tees in the branch 
connection. 

DO NOT connect boiler piping to the 
tee through connections as shown 
at right. The system will not work 
correctly this way.

The circulator supplied with the boiler (

a

) must be 

used only in the boiler secondary loop as shown in the 
schematic above and in the manual. System (

b

) and zone 

circulators and DHW circulator (

c

) must be supplied by 

the installer. Above right is a typical installation, showing 
the near-boiler piping and connection to the system.

Boiler loop piping must be sized to the minimums 

listed in the boiler manual. Using smaller piping will 
cause performance problems.

Ultra-80   /  Ultra-105

• 

 .  .  .  .  .  use 1” or larger

Ultra-155 /  Ultra-230

• 

.  .  .  .  . use 1¼” or larger

Ultra-299 /  Ultra-399

• 

.  .  .  .  . use 1½” or larger

WATER PIPING

(see boiler manual for details)

22

WRONG

RIGHT

DHW

DHW

System

Sensor

Sensor

Gas

System

Typical piping, zone-valve zoning

Do not exceed 
12 inches apart

Optional 
Easy-Up Manifolds: 
1¼” 

(W-M #383-500-649)

 

1½” 

(W-M #383-500-661)

Do not e

xceed 

12 inches apar

t

b

a

c

a

b

c