Weil-McLain PEG 5 Series User'S Information Manual Download Page 20

20

Part No. 550-142-801/1112

Weil-McLain

500 Blaine Street

Michigan City, IN 46360-2388

http://www.weil-mclain.com

Common problems and solutions

Symptom

Common Causes

Possible Corrections

Rapid cycling — 

boiler turns on and 

off frequently

Thermostat installed where drafts 

or heat affect reading

Locate thermostat on inner wall away from heat sources or cool 

drafts.

Heat anticipator in thermostat 

adjusted incorrectly

Adjust thermostat per manufacturer's instructions.

Incorrect limit setting

Set limit according to system needs. Maximum setting is 220°F. 

Increase limit setting to decrease cycling.

Insufficient water flow through 

boiler

Check all valves to and from boiler. Return to proper setting.

Confirm circulator size.

Frequent release of 

water through relief 

valve

Expansion tank sized too small

Call qualified service technician to check expansion tank 

operation and size.

Flooded expansion tank

Call qualified service technician to check expansion tank 

operation.

Inoperative limit control

Call qualified service technician to replace limit control.

Need to frequently 

add makeup water

Leaks in boiler or piping

Have qualified service technician repair leaks at once to avoid 

constant use of makeup water. Makeup water can cause 

mineral deposits which, in turn, can cause boiler section failure. 

Do not use petroleum-base stop-leak compounds.

Black water 

condition

Oxygen corrosion due to leaks in 

boiler and piping

Have qualified service technician repair at once. Keep pH of 

water between 7.0 to 8.5.

Popping or 

percolating noise 

heard in boiler

Mineral deposits in sections due 

to constant use of makeup water

Call qualified service technician to de-lime boiler, if necessary. 

In some cases, deposits will be too heavy to remove with de-

liming procedures.

Have qualified service technician repair leaks to eliminate need 

for constant makeup water.

Incorrect pH of boiler water

Call qualified service technician to check pH level and correct. 

pH should be maintained between 7.0 to 8.5.

Insufficient water flow through 

boiler

Check all valves to and from boiler. Return to proper setting.

Confirm circulator size.

Metal flakes found in 

vent outlet or vent — 

flueway corrosion

Contaminated combustion air 

supply — See page 3 in this 

manual.

Remove any contaminating products. See page 3 in this 

manual.

Provide outside air for combustion. 

Condensation of combustion 

gases in boiler sections

Have qualified service technician inspect system piping and 

controls to verify proper regulation of return water temperature.

Some radiators or 

baseboard units do 

not heat or are noisy

Air in system

Bleed air from system through air vents in radiators or 

baseboard units.

Low system pressure

Fill to correct pressure.

Check for leaks in boiler or piping. Have qualified service 

technician repair at once.

High limit set too low

Adjust high limit to higher setting.

Summary of Contents for PEG 5 Series

Page 1: ...fire department Installation and service must be performed by a qualified installer service technician or the gas supplier If the information in this manual is not followed exactly a fire or explosion...

Page 2: ...sonal injury death or substantial property damage Indicates presence of hazards that can cause severe personal injury death or substantial property damage Indicates presence of hazards that will or ca...

Page 3: ...ler or piping must be repaired at once to prevent makeup water Do not add cold water to hot boiler Thermal shock can cause sections to crack Boiler operation Do not block flow of combustion or ventila...

Page 4: ...fold orifices 5 Control module 6 Inducer CGi only 7 Vent damper CGa only 8 Water temperature sensor 9 Transformer 10 Spill switch CGa only 11 Air pressure switch CGi only 12 Rollout thermal fuse eleme...

Page 5: ...burner 3 Main burner 4 Gas manifold orifices 5 Control module 7 Vent damper 9 Transformer 10 Spill switch 12 Rollout thermal fuse element 13 Low water cutoff steam boilers 14 Limit control s 15 Draft...

Page 6: ...only by a qualified service technician Owner maintenance see following pages for instructions A nnual start up Inspect Reported problems Boiler area Air openings Flue gas vent system Pilot and main b...

Page 7: ...echnician to inspect the boiler and vent system for possible damage from acid corrosion If products cannot be removed immediately call a qualified service technician to install an outside combustion a...

Page 8: ...ators relief valve and other fittings Immediately call a qualified service technician to repair any leaks 1 Visually inspect all parts or the flue gas venting system for any signs of blockage leakage...

Page 9: ...ot flame sensor spark ignited pilot 3 Thermocouple or thermopile or pilot flame sensor glowing cherry red Improper pilot flame 1 Overfired Large flame lifting or blowing past pilot flame sensor 2 Unde...

Page 10: ...turn thermostat to normal setting Test low water cutoff all steam boilers water boilers if installed If the system is equipped with a low water cutoff test the low water cutoff periodically during the...

Page 11: ...to clean the valve seat If the valve continues to weep afterwards contact your qualified service technician to inspect the valve and system 5 If water does not flow from the valve when you lift the le...

Page 12: ...tempt to light the pilot Use caution when attempting to light the propane pilot This should be done by a qualified service technician particularly if pilot outages are common Periodically check the od...

Page 13: ...tat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove from panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light...

Page 14: ...at to lowest setting 3 Turn off all electrical power to the appliance 4 Remove front panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light...

Page 15: ...wer to the appliance 4 Remove front panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand 6 Depress gas control knob sli...

Page 16: ...CGa CGi EG EGH LGB PEG Boilers 16 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot Gas valve Robertshaw 7200 CGa 25 to CGa 6 EG 30 to EG 50 PEG 30 to PEG 50...

Page 17: ...User s Information Manual 17 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot Gas valve Robertshaw 7000DERHC EGH 85 to EGH 125...

Page 18: ...the thermostat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove jacket front panel 5 This appliance is equipped with an ignition device which automatically lights the burner...

Page 19: ...User s Information Manual 19 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot LGB...

Page 20: ...se stop leak compounds Black water condition Oxygen corrosion due to leaks in boiler and piping Have qualified service technician repair at once Keep pH of water between 7 0 to 8 5 Popping or percolat...

Reviews: