Weil-McLain PEG 5 Series User'S Information Manual Download Page 1

Do not store or use 

gasoline or other flammable vapors and liquids

 in the 

vicinity of this or any other appliance.

WHAT TO DO IF YOU SMELL GAS

• 

Do not try to light any appliance

.

• 

Do not touch any electrical switch

do not use any phone

 in your 

building.

• 

Immediately 

call your gas supplier from a neighbor’s phone

. Follow 

the gas supplier’s instructions.

• 

If you cannot reach your gas supplier, call the fire department

.

Installation and service must be performed by a qualified installer, service 

technician or the gas supplier.

 

If the information in this manual is not followed exactly, a fire or 

explosion may result, causing property damage, personal injury or 

loss of life.

CGa

 

Series 2,

 

CGi

 

Series 3,

 

EG 

Series 5,

 

EGH

 

Series 5,

LGB

 

Series 2,

 

PEG

 

Series

 5

 

Gas-Fired Boilers

User’s 

Information 

Manual

Part Number 550-142-801/1112

INSTALLER:

Please take time to review this User’s information

Manual with the boiler owner. Explain all maintenance 

and service procedures and the correct Operating 

Instructions.

Summary of Contents for PEG 5 Series

Page 1: ...fire department Installation and service must be performed by a qualified installer service technician or the gas supplier If the information in this manual is not followed exactly a fire or explosion...

Page 2: ...sonal injury death or substantial property damage Indicates presence of hazards that can cause severe personal injury death or substantial property damage Indicates presence of hazards that will or ca...

Page 3: ...ler or piping must be repaired at once to prevent makeup water Do not add cold water to hot boiler Thermal shock can cause sections to crack Boiler operation Do not block flow of combustion or ventila...

Page 4: ...fold orifices 5 Control module 6 Inducer CGi only 7 Vent damper CGa only 8 Water temperature sensor 9 Transformer 10 Spill switch CGa only 11 Air pressure switch CGi only 12 Rollout thermal fuse eleme...

Page 5: ...burner 3 Main burner 4 Gas manifold orifices 5 Control module 7 Vent damper 9 Transformer 10 Spill switch 12 Rollout thermal fuse element 13 Low water cutoff steam boilers 14 Limit control s 15 Draft...

Page 6: ...only by a qualified service technician Owner maintenance see following pages for instructions A nnual start up Inspect Reported problems Boiler area Air openings Flue gas vent system Pilot and main b...

Page 7: ...echnician to inspect the boiler and vent system for possible damage from acid corrosion If products cannot be removed immediately call a qualified service technician to install an outside combustion a...

Page 8: ...ators relief valve and other fittings Immediately call a qualified service technician to repair any leaks 1 Visually inspect all parts or the flue gas venting system for any signs of blockage leakage...

Page 9: ...ot flame sensor spark ignited pilot 3 Thermocouple or thermopile or pilot flame sensor glowing cherry red Improper pilot flame 1 Overfired Large flame lifting or blowing past pilot flame sensor 2 Unde...

Page 10: ...turn thermostat to normal setting Test low water cutoff all steam boilers water boilers if installed If the system is equipped with a low water cutoff test the low water cutoff periodically during the...

Page 11: ...to clean the valve seat If the valve continues to weep afterwards contact your qualified service technician to inspect the valve and system 5 If water does not flow from the valve when you lift the le...

Page 12: ...tempt to light the pilot Use caution when attempting to light the propane pilot This should be done by a qualified service technician particularly if pilot outages are common Periodically check the od...

Page 13: ...tat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove from panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light...

Page 14: ...at to lowest setting 3 Turn off all electrical power to the appliance 4 Remove front panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light...

Page 15: ...wer to the appliance 4 Remove front panel 5 This appliance is equipped with an ignition device which automatically lights the pilot Do not try to light the pilot by hand 6 Depress gas control knob sli...

Page 16: ...CGa CGi EG EGH LGB PEG Boilers 16 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot Gas valve Robertshaw 7200 CGa 25 to CGa 6 EG 30 to EG 50 PEG 30 to PEG 50...

Page 17: ...User s Information Manual 17 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot Gas valve Robertshaw 7000DERHC EGH 85 to EGH 125...

Page 18: ...the thermostat to lowest setting 3 Turn off all electrical power to the appliance 4 Remove jacket front panel 5 This appliance is equipped with an ignition device which automatically lights the burner...

Page 19: ...User s Information Manual 19 Part Number 550 142 801 1112 Operating instructions Spark ignited pilot LGB...

Page 20: ...se stop leak compounds Black water condition Oxygen corrosion due to leaks in boiler and piping Have qualified service technician repair at once Keep pH of water between 7 0 to 8 5 Popping or percolat...

Reviews: