![Weil-McLain Evergreen EVG 220 Manual Download Page 86](http://html1.mh-extra.com/html/weil-mclain/evergreen-evg-220/evergreen-evg-220_manual_952700086.webp)
Startup — fill the system
Part number 550-100-131/0120
– 86 –
®
gas
-
fired
water
boiler
— 220/299/300/399
Boiler Manual
Chloride concentration requirement
1. Filling with chlorinated fresh water should be acceptable since
drinking water chloride levels are typically less than 5 ppm.
2. Do not use the boiler to directly heat swimming pool or spa
water.
3. Do not fill boiler or operate with water containing chloride
in excess of 200 ppm.
Verify that the water chemistry meets the limita-
tions and requirements of all other equipment in
the system.
Antifreeze
1. Use only antifreeze listed by Weil-McLain as suitable for use
with
Evergreen
®
Gas Boilers. See Figure 111, page 117 for
information.
2. See Replacement parts at the end of this manual for
Weil-McLain part numbers to obtain antifreeze through a
Weil-McLain distributor.
Use the correct amount of antifreeze
1. Determine the freezing temperature needed (to protect against
lowest likely temperature the system water will encounter).
2. Find the antifreeze concentration by volume needed for this
temperature from the antifreeze manufacturer’s data on the
antifreeze container.
3. Add up the volume (gallons) of all system piping and compo-
nents, including the expansion tank and boiler.
a. Boiler water content is listed in Figure 124, page 130.
b. Remember to include expansion tank water content.
4. Multiply this volume by the (percent) antifreeze needed to find
the number of gallons of antifreeze to add.
Fill and test water system
1. Fill system only after ensuring the water meets the require-
ments of this manual.
2. Close manual and automatic air vents and boiler drain valve.
3. Fill to correct system pressure. Correct pressure will vary with
each application.
a. Typical cold water fill pressure for a residential system is
12 psig.
b. Pressure will rise when boiler is turned on and system water
temperature increases.
c. Pressure should
NOT
exceed 24 psig when using as
shipped, 30 psig relief valve.
d. Operating pressure should be no higher than 80% of the
relief valve setting for most systems. Operating pressure
must never exceed 80 PSIG.
4. At initial fill and during boiler startup and testing, check system
thoroughly for any leaks. Repair all leaks before proceeding
further.
Eliminate all system leaks. Continual fresh make-up
water will reduce boiler life. Minerals can build up in
the heat exchanger, reducing heat transfer, overheat-
ing heat exchanger, and causing heat exchanger failure.
Purge air from water system
1. Connect a hose to the purge valve (see purge/drain valves, item
11, in piping diagrams beginning on page 43). Route hose to
an area where water can drain and be seen.
2. Close the boiler or system isolation valve between the purge
valve and fill connection to the system.
Clean system to remove sediment
1. You must thoroughly flush the system (without boiler
connected) to remove sediment. The high-efficiency heat
exchanger can be damaged by buildup or corrosion due to
sediment.
If the system needs to be cleaned, we recom-
mend using Sentinel X400 cleaner, available from
Weil-McLain. See Figure 111, page 117 for infor-
mation. Follow instructions supplied with the
X400 cleaner.
2. For zoned systems, flush each zone separately through a
purge valve. (If purge valves and isolation valves are not
already installed, install them to properly clean the system.)
3. Flush system until water runs clean and you are sure piping
is free of sediment.
Do not use petroleum-based cleaning or seal-
ing compounds in boiler system. Damage to
elastomer seals and gaskets in system could oc-
cur, resulting in substantial property damage.
Before filling the boiler and system with water,
verify the following.
DO NOT fill with soft-
ened water.
Boiler corrosion can occur.
Failure to comply could result in boiler failure
or unreliable operation.
Water chemistry
Water pH requirements
1. Maintain boiler water pH between 7.0 and 8.5. Check with
litmus paper or have chemically analyzed by water treat-
ment company.
2. If pH differs from above, consult local water treatment
company for treatment needed.
Hardness requirements
1. Consult local water treatment companies for unusually hard
water areas (above 7 grains hardness).
Figure 86
Tools needed for start-up
Tool
Purpose
#2 Phillips
screwdriver
Multiple uses
Flat blade
screwdriver
To assemble the condensate trap
Multimeter
Measurements on sensors and electrical com-
ponents
Manometer
(Inclined or digital)
Measure the INLET gas pressure to the boiler
Combustion analyzer
(Digital preferred)
Combustion testing and boiler adjustments
Contact thermometer
Checking surface temperatures of heat exchanger
and pipes