Part number 550-100-131/0120
– 74 –
®
gas
-
fired
water
boiler
— 220/299/300/399
Boiler Manual
Figure 72
Evergreen control settings available in BASIC MODE (see Advanced Manual for ADVANCED MODE settings)
Available control settings and system presets
Figure 73
System types available in BASIC MODE (each option shown with factory settings)
Available settings from CONTRACTOR MENU
Boiler Settings Menu
Priority 2 menu
Assign Inputs menu
• Boiler Model
• Inputs Assigned (non-selectable)
Input 1: TT1
• Control Type
• System Type
• Priority 1, 2 or 3
• High Altitude
• Target Mod Sensor (non-selectable)
• Source (TT1 or 0-10v)
• LP Gas
• Target Adjust (non-selectable)
• AUX PUMP/OUTPUT
• ODT Sensor Exempt
• Supply Max
• Off
• Manual Reset High Limit Temp
• Supply Min (not available for DHW) *
• WWSD Temp
• OD Reset Max (or Volts for Max) *
Input 2: TT2 and Input 3:TT3
• Adjust Outdoor
• OD Reset Min (or Volts for Min) *
• Priority 1, 2 or 3
• Circulator Exercising
• Boost Time *
• AUX PUMP/OUTPUT
• Freeze Protect Circs
• Off
• Reset Factory Default
Priority 3 menu
• Inputs Assigned (non-selectable)
Diagnostics menu
Priority 1 menu
• System Type
• See Figure 80, page 80 for details.
• Inputs Assigned (non-selectable)
• Target Mod Sensor (non-selectable)
• System Type
• Target Adjust (non-selectable)
Maintenance Info menu
• Target Mod Sensor (non-selectable)
• Supply Max
• See Figure 85, page 85 for details.
• Target Adjust (non-selectable)
• Supply Min (not available for DHW) *
• Supply Max
• OD Reset Max (or Volts for Max) *
Set Date and Time menu
• Supply Min (not available for DHW) *
• OD Reset Min (or Volts for Min) *
• See Figure 85, page 85 for details.
• OD Reset Max (or Volts for Max) *
• Boost Time *
• OD Reset Min (or Volts for Min) *
* These items only appear in the menus if Target Adjust is active.
• Boost Time *
System Type
8-Character
Abbreviation
3-Character
Abbreviation
Supply Max
°F
OD Reset
Min °F
Supply
Min °F
OD Reset
Max °F
Run
Boiler Pump
Run AUX
PUMP/
OUTPUT
Fan-coil
FAN-COIL
FCL
180
0
140
70
YES
YES
Finned Tube Baseboard
FIN BASE
FTB
180
0
130
70
YES
YES
Cast Iron Baseboard
IRONBASE
CIB
180
0
120
70
YES
YES
Cast Iron Radiators
RADIATOR
CIR
180
0
120
70
YES
YES
Radiant - slab on grade
RAD SLAB
RSG
120
0
80
70
YES
YES
Radiant - thin slab
RAD SLAB
RTS
140
0
80
70
YES
YES
Radiant - below floor
(staple up)
RADFLOOR
RSU
160
0
90
70
YES
YES
Radiant - above floor
(sleeper system)
RADFLOOR
RAF
140
0
90
70
YES
YES
Domestic Hot Water
DOMESTIC
DHW
180
N/A
N/A
N/A
NO
NO
Custom (user defined)
XXXXXXXX
(user input)
first three of
user input
180
0
70
70
YES
YES