Figure 77
Evergreen BASIC mode ASSIGN INPUT options (USER MODE must be set to BASIC) — see
Figure 78, page 79 and Figure 79, page 79 for explanation of AUX PUMP/OUTPUT settings
Screens shown above are typical only.
Actual screens depend on control
settings chosen.
Part number 550-100-131/0120
– 78 –
®
gas
-
fired
water
boiler
— 220/299/300/399
Boiler Manual
ASSIGN INPUTS menu, BASIC mode
Boiler Model, Altitude and Fuel Type are criti-
cal settings.
Failure to set correctly could result in
severe personal injury, death or substantial property
damage.
1. Access contractor menus by pressing and holding the UP and
DOWN arrow keys at the same time for 7 seconds.
2. See Figure 74, page 75 for the screen sequences up to the
CONTRACTOR menu.
MENU ITEM
DESCRIPTION
Overview
• There are three priority levels defined by the settings
chosen in Figure 76, page 77.
• For DHW priority, make sure PRIORITY 1 is defined
for a DHW system.
• If DHW priority is required and analog input (0-10v
remote modulation) is used for space heating, wire the
DHW aquastat to Input 2 (TT2) and assign INPUT 2
as PRIORITY 1 and INPUT 1 as PRIORITY 2 with
SOURCE set to 0-10V.
INPUT 1
• Assign priority (system type) for INPUT 1 — options are:
• PRIORITY 1 — assigns INPUT 1 to PRIORITY 1 system.
• PRIORITY 2 — assigns INPUT 1 to PRIORITY 2 system
• PRIORITY 3 — assigns INPUT 1 to PRIORITY 3 system
• AUX PUMP/OUTPUT
• OFF
• NOTE: For INPUT 1 only, select SOURCE = TT1 for
thermostat input or 0-10V if analog input is required.
INPUT 2
• Assign priority (system type) for INPUT 2 — options are:
• PRIORITY 1 — assigns INPUT 2 to PRIORITY 1 system.
• PRIORITY 2 — assigns INPUT 2 to PRIORITY 2 system
• PRIORITY 3 — assigns INPUT 2 to PRIORITY 3 system
• AUX PUMP/OUTPUT
• OFF
INPUT 3
• Assign priority (system type) for INPUT 3 — options are:
• PRIORITY 1 — assigns INPUT 3 to PRIORITY 1 system.
• PRIORITY 2 — assigns INPUT 3 to PRIORITY 2 system
• PRIORITY 3 — assigns INPUT 3 to PRIORITY 3 system
• AUX PUMP/OUTPUT
• OFF