CGt
GAS-FIRED WATER BOILER — Series 2 —
Boiler Manual
Troubleshooting — control module lights
(cont.)
12c
CHART 5 –– PRESS SWITCH
light flashing and POWER light on steady
–– Usually indicates pressure switch opened during run cycle ––
–– May also be caused by wind gusts in excess of 40 mph for non-direct vent sidewall-vented boilers ––
Electrical shock hazard
— Wherever you see ▲
TURN OFF POWER
▲, follow the instructions. Failure to follow
instructions could result in severe personal injury, death or substantial property damage.
• Reset boiler control by turning off power at service switch or turning down thermostat for at least 45 seconds.
• Thermostat should call for heat and appropriate zone valves open.
Does inducer motor operate?
No
Yes
• Inspect and check wire
harness from control
module to pressure switch.
• Reseat connector in control
module receptacle.
• If harness is intact and
properly seated, but
problem persists, replace
control module.
• Retest.
• Check air pressure switch per manual Section 12b,
page 46.
• Replace if necessary. Retest.
• Clear vent and recycle boiler.
• Recheck boiler operation.
• Replace inducer
assembly.
• Retest.
• Boiler should be in
normal operating
sequence.
• Observe operation until
thermostat is satisfied
and inducer has
completed its post-
purge cycle.
• Remove
INDUCER
plug (Figure 33
, Item 6
, page 48)
from plug receptacle of control module.
• Place voltmeter leads across the
120VAC N
and
120VAC H
pins of the
INDUCER
receptacle (left col-
umn center and right column bottom pins).
Does the voltmeter indicate
120VAC
?
No
Yes
• Remove one of the wires connected to the pressure
switch.
• Check continuity across the switch terminals.
Does the ohmmeter indicate the switch is closed?
No
Yes
• Wait 5 minutes.
Is
PRESS SWITCH
light flashing?
No
Yes
Is vent blocked?
No
Yes