GAS-FIRED WATER BOILER — Series 2 —
Boiler Manual
Troubleshooting — common problems
12d
Common Problems
Common Causes
Possible Corrections
Rapid cycling — burner
turns on and off
frequently.
Thermostat installed where
drafts or heat affect reading.
Locate thermostat on inner wall
away from heat sources or cool
drafts.
Heat anticipator in
thermostat adjusted
incorrectly.
Adjust heat anticipator to match
current draw. Refer to boiler
wiring diagram.
Incorrect high limit setting.
Have qualified service
technician increase limit setting
to decrease cycling. Maximum
setting 220°F.
Need to frequently add
makeup water.
Leaks in boiler or piping.
Have qualified service
technician repair leaks at once
to avoid constant use of makeup
water.
Popping or percolating
noise heard in boiler.
Mineral deposits in sections
due to constant use of
makeup water, or incorrect
pH.
Have qualified service
technician repair leaks at once
to avoid constant use of makeup
water and check pH (between
7.0 and 8.5).
Black water condition.
Oxygen corrosion due to
leaks in piping.
Have qualified service
technician repair leaks at once
to avoid constant use of makeup
water and check pH (between
7.0 and 8.5).
Frequent release of
water through relief
valve.
Expansion tank sized too
small or water-logged.
Have qualified service
technician check expansion
tank operation.