background image

Part number 550-141-402/0801

3

CER Series 2 Electric-Hydronic Boilers Installation Instructions

Mounting the boiler

Normally, the boiler will be installed against a frame or
masonry wall.  If the wall surface is rough or uneven, it
may be necessary to mount plywood on the wall, then
mount the boiler on the plywood.  Refer to
“Dimensions” and “Ratings” on page 13, and note the
boiler weight.  Be sure that the wall structure will
support the boiler and its piping.
The 

9

/

16

" top mounting holes and 

5

/

16

" lower mounting

holes are on 16-inch centers to permit installation on
studs in standard wall construction.  The use of ¼" x
2½" lag screws is recommended for mounting the boiler.
The head diameters of the top two screws must not
exceed 

9

/

16

".

1.

Locate the top mounting holes so that the boiler
will be level.   Install the screws so that the heads
protrude ¾" from the wall.

2.

Raise the boiler to mounting position by placing a
board across the bottom of the boiler or by grasping
the lower left and right inside corners. Do not
attempt to lift the boiler by grasping the bottom
jacket cross tie.

3.

Place the top brackets over the lag screws and then
install screws through the lower mounting holes.
The top screws can now be tightened.

Locating the boiler

The compact construction of the electric-hydronic
boiler permits installation in an alcove, storeroom or
other small area.  The location chosen should have
convenient electrical service.
A minimum of 6 inches is required at the top of the
boiler for installation and accessories.  A clearance of
18 inches is required on the right hand side for removal
of the elements, and a 2-inch clearance is required
beneath the boiler for ventilation.

General instructions

The Weil-McLain Model CER electric-hydronic boilers
are assembled and tested units designed for use in forced
hot water heating systems.  The CER is supplied without
circulator or expansion tank.
Low flow rates through the boiler at elevated
temperatures should be avoided.  The structure to be
heated should be insulated in the conventional manner
used in your area for electrically heated buildings.  Boiler
must be installed in accordance with these instructions
so as not to void our warranty.
Open the boiler crate and check the contents.  In the
event of shortage or damage, notify the transportation
company immediately.

Expansion tank sizing

Undersized expansion tanks cause system water to be
lost from relief valve and makeup water added through
fill valve.  Eventual section failure can result.

If a Fill-Trol system is used, refer to Table 1 for proper sizing.  If Fill-Trol
action is not desired, size the expansion tank according to the water volume
of the system.

Table 1

Expansion tank sizing (Tank sizing based on 200 °F
average system temperature.)

Hydrostatic pressure test

Pressure test boiler before attaching piping or electrical supply.

1.

Install air vent in tapping on top of boiler.

2.

Plug remaining tappings, including relief valve opening.

3.

Connect water supply.  Fill boiler and purge all air.  For more than 10
minutes, pressure-test at 1½ times maximum working pressure.

Do not leave boiler unattended.  Cold water fill could
expand and cause excess pressure, resulting in severe
personal injury, death or substantial property damage.

4.

Check for maintained gauge pressure.  Visually check for leaks if gauge
pressure drops.

5.

Drain boiler and repair leaks if found.

Leaks must be repaired at once.  Failure to do so can
damage boiler, resulting in substantial property damage.

6.

Retest boiler after repairing leaks.

7.

Remove testing plugs and air vent.

Do not use petroleum-based cleaning or sealing
compounds in boiler system.  Severe damage to boiler
will result, causing substantial property damage.

Pre-installation

Boiler
model
number

Standard Fill-Trol tank

(for series loop or one-pipe system 

with convector baseboard)

Additional Fill-Trol tank

(for cast-iron radiators or 

cast-iron baseboard)

CER-24

No. 109

No. 110

CER-32

No. 109

No. 110

CER-40

No. 109

No. 110

Note: Gravity systems converted to a forced hot water system usually require 

additional compression tank capacity.

Summary of Contents for CER Series 2

Page 1: ...el and the CP number from the boiler jacket You may list the CP number in the space provided on the Installation and service certificate found on page 10 Installer Read all instructions before installing Follow all instructions in proper order to prevent personal injury or death Consider piping and installation when determining boiler location Any claims for damage or shortage in shipment must be ...

Page 2: ...es section failure Addition of oxygen and other gases can cause internal corrosion Leaks in boiler or piping must be repaired at once to prevent makeup water Do not add cold water to hot boiler Thermal shock can cause sections to crack Glycol potential fire hazard All glycol is flammable when exposed to high temperatures If glycol is allowed to accumulate in or around the boiler or any other poten...

Page 3: ...ted temperatures should be avoided The structure to be heated should be insulated in the conventional manner used in your area for electrically heated buildings Boiler must be installed in accordance with these instructions so as not to void our warranty Open the boiler crate and check the contents In the event of shortage or damage notify the transportation company immediately Expansion tank sizi...

Page 4: ...g or servicing The Model CER electric hydronic boilers are pre wired and require only two wires for connection of single phase boilers and three wires for connection of 3 phase boilers Aluminum wire must not be used Add additional 120 volt service must be provided to utilize the circulator control provided in the boiler See wiring diagram on page 6 for single phase or page 7 for 3 phase An opening...

Page 5: ...nds Call for heat satisfied 5 The thermostat contacts open de energizing the first contactor 2K the circulator relay 1K and the heater in the first thermal time delay H1 6 After a minimum of 10 seconds the contacts in the first thermal delay 1C open instantly de energizing the electronic time delay ED1 the second contactor 3K and the second thermal delay heater H2 7 This sequence continues until a...

Page 6: ...tate or local code requirements 3 All safety circuit wiring must be N E C Class 1 4 Use only copper conductors for power input wiring Do not use aluminum conductors 5 For 208 volt power supply remove orange wire and replace with red wire 6 Maximum circulator motor is 1 6 horsepower 1C 2C 4C TD1 ED1 ED2 ED3 ED4 CONTACTORS THERMAL TIME DELAY RELAYS ELECTRONIC TIME DELAY RELAYS HEATING ELEMENTS HEATI...

Page 7: ... Class 1 4 Use only copper conductors for power input wiring Do not use aluminum conductors 5 For 208 volt power supply remove orange wire and replace with red wire 6 Maximum circulator motor is 1 6 horsepower 1C 2C 4C TD1 ED1 ED2 ED3 ED4 CONTACTORS THERMAL TIME DELAY RELAYS ELECTRONIC TIME DELAY RELAYS HEATING ELEMENTS 1K1 1K TD2 TD3 TD4 H1 H2 H3 H4 2K1 2K 3K 4K 5K 6K 3K1 4K1 5K1 6K1 2K2 3K2 4K2 ...

Page 8: ...has a shorted coil To isolate the trouble proceed as follows a Check contactor Connect a jumper from terminal 3 of the electronic delay to the transformer wire going to terminal B on the low side of the limit control b If the contactor energizes check electronic and thermal delays Remove the jumper from the transformer terminal and touch it to terminal 1 of the electronic delay The jumper now conn...

Page 9: ...and automatic air vent if used 2 Fill the boiler and system to an initial pressure of about 12 pounds per square inch 3 Open automatic air vent one turn if used 4 Starting on the lowest floor open air vents one at a time until water squirts out Close vent 5 Repeat with remaining vents 6 Refill to correct pressure Freeze protection when used See WARNING on page 2 for important information regarding...

Page 10: ...Date installed _______________ Measured Btuh input ____________ Installer ________________________ ________________________________ ______________________________ company address phone _____________________________________ installer s signature Installation and service certificate Check limit control operation by lowering the control settings as described in the Troubleshooting section on page 8 R...

Page 11: ... to be lost from relief valve and makeup water added through fill valve Eventual section failure can result If the relief valve opens frequently check the expansion tank If the system has a pressurized tank with a rubber diaphragm separating the air cushion from the water an Ex Trol or equivalent tank use a tire pressure gauge to check the air charging valve on the end of the tank If water flows t...

Page 12: ... dust respirator N95 This type of respirator is based on the OSHA requirements for fiberglass wool at the time this document was written Other types of respirators may be needed depending on the job site conditions Current NIOSH recommendations can be found on the NIOSH web site at http www cdc gov niosh homepage html NIOSH approved respirators manufacturers and phone numbers are also listed on th...

Page 13: ...0 C field wiring Notes 1 and 2 Total amperes Boiler water content Approximate shipping wt KW 208V 240V 480V 208V 240V 480V 208V 240V 480V Gallons lbs Single phase CER 24 82 000 24 3 50 50 1 2 116 101 5 2 170 CER 32 109 000 32 4 50 50 00 0 154 134 5 2 170 C ER 40 137 000 40 5 50 50 000 000 192 167 5 2 170 3 phase CER 24 82 000 24 3 30 30 JKS 15 4 4 8 67 58 29 5 2 170 CER 32 109 000 32 4 30 30 JKS 1...

Page 14: ...n Weil McLain part number Item number Description Weil McLain part number 1 Control tray 428 800 000 6 Jacket element cover plate 428 800 015 2 Boiler casting with insulation 318 806 200 7 Jacket bottom panel 428 600 004 3 Jacket door 428 600 006 8 Jacket bottom cross tie 428 800 010 4 Jacket side and back panel 428 600 008 9 Element opening cover plate 590 243 200 5 Jacket top panel 428 600 002 1...

Page 15: ...t 511 842 362 Relief valve 511 546 924 Temperature pressure gauge 510 218 099 Element contactor 208 240 volt single phase 512 150 148 Element contactor 3 phase 512 050 015 Line terminal and fuse block single phase 512 050 016 Line terminal and fuse block 208 240 volt 3 phase 512 050 017 Line terminal and fuse block 480 volt 3 phase 591 550 229 8KW heating element 208 volt single phase and 3 phase ...

Reviews: