5
Opening of the Enclosure
Place enclosure in a vertical upright position. Loosen the lid cover fixings
screws with a suitable tool (refer to diagram 1 below). After loosening the
covers screws, the lid can be opened up to approximately 130°.
Removing the lid
The lid should be removed by loosening the cover fixing screws and any
attached lid bonding cable with a suitable tool. After loosening the fixing
screws the cover lid must be opened to a 90° position (refer to diagram 2
below). With the lid in this position, lift the lid slightly and slide to the outside
to release (refer to diagram 3 below). In this way you are able to fix the lid
to either the left or the right hand side of the enclosure (multi hinge version
only). If the lid position is to be fixed to another side, it is also necessary to
reposition the padlock lug to the opposite side. Do not remove the captive
element of the screws!
1
2
3
Removing gland plates
If gland plates are to be used remove them by loosening the gland plate
screws with a suitable tool. Afterwards the plates can be detached.
Closing the enclosure
Ensure that all lid, gland plate, earth stud screws are fully tightened in a
crosswise manor after installation.
Tightening Values
Lid & Gland plates (when present)
2.5 Nm
M10 earth stud (out-/inside)
15.0 Nm
M6 earth stud inside
6.0 Nm
Summary of Contents for Klippon TB MH
Page 2: ......
Page 43: ...43 316L 1 4404 304 1 4301 60 C 135 C IP IP 66 67 IP67 105 C ATEX...
Page 45: ...45 1 130 90 2 3 MH 1 2 3 2 5 10 15 0 6 6 0...
Page 46: ...46 IP ATEX IECEx IP KTB MH 765015 C D 60...
Page 49: ...49 G F E A C B D G E F G A 1 x M10 B 1 x 20 t 2 C 1 x D 1 x 20 E 2 x F 2 x 15 G 3 x M10 15 6 0...
Page 50: ...50...
Page 51: ......