Testing the product
44
5662300000/01/08.10
9.1 Test
procedure
Following equipment is necessary to test the WAVE TTA:
•
WAVE TTA Module:
WAS 6 TTA (Order No. 8939670000) or WAZ 6 TTA (Order No. 8939680000)
WAS 6 TTA EX (Order No. 8964310000) or WAZ 6 TTA EX (Order No. 8964320000)
•
USB Interface unit CBX100 USB or CBX200 USB (for configuration)
•
Power supply - see chapter
165H165H165H
5.3
(e.g. 24 V DC, such as model CP SNT 12 W (Order No. 9918840024))
•
Configuration Software TTA Set (for configuration)
•
PC or Laptop, (for configuration)
•
To test input to output transfer function an appropriate input signal source is needed, such as:
- Calibrator Portacal 1000 (Order No. 7940010194) for DC current and Voltage input signals
- Potentiometer e.g. 5 k
Ω
- Resistance
box
- Thermocouple source or "Millivolts source”
•
Output meter (e.g. a dvm) to measure the range of voltage or current produced.
NOTICE
Depending on the measurement accuracy required from the WAVE TTA, the input signal source
and output meter errors should sum to typically better than 1/3 of the accuracy required.
1
Mount the WAVE TTA with the power supply on a DIN rail and consider the following connection diagram
in chapter
166H166H166H
6.
2
Connect the input sensor e.g. potentiometer, and output meter.
3
For configuration, install TTA Set configuration software as shown in the chapter
167H167H167H
8.
Summary of Contents for WAVE TTA
Page 1: ...WAVE TTA Manual...
Page 2: ......
Page 6: ...Contents 6 5662300000 01 08 10...
Page 16: ...Introduction 16 5662300000 01 08 10...
Page 22: ...Operation 22 5662300000 01 08 10...
Page 28: ...Installation 28 5662300000 01 08 10...
Page 46: ...Testing the product 46 5662300000 01 08 10...
Page 47: ...Troubleshooting 5662300000 01 08 10 47 10 Troubleshooting 10 1 Troubleshooting 168H168H168H48...
Page 53: ......