Setup / Configuration 

30 

  

5662300000/01/08.10 

7.1 Default 

setting 

 

Input range  

4-20 mA 

ADS Speed 

medium 

Transfer function 

Linear 

Response time 

0.25 s 

Output range 

4-20 mA 

Action  

direct 

Low limit 

0 mA 

High Limit 

20 mA 

Output @ error 

21.5 mA 

Digital outputs 1 and 2 

Disabled 

Table 8 

Default settings 

7.2 

CBX100 USB and CBX200 
USB introduction 

The CBX100 USB or CBX200 USB is the configura-
tion interface for the WAVE TTA. This is the same 
interface as can be used for configuring the ITX Plus 
universal transmitter. 
Connection to the computer is via USB port, and to 
the WAVE TTA via a jack connector. Tx and Rx 
status are indicated by LEDs on the CBX100 USB or 
CBX200 USB. 
 
 
 
 
 
 
 
 
 
 

7.3 

Configuration / diagram wiring 

 

 

Figure 7 

Configuration / diagram wiring 

Summary of Contents for WAVE TTA

Page 1: ...WAVE TTA Manual...

Page 2: ......

Page 3: ...ition 1 0 08 10 WAVE TTA EX products complemented and edito rial changes Contact address Weidm ller Interface GmbH Co KG Postfach 3030 32720 Detmold Klingenbergstra e 16 32758 Detmold Germany Phone 49...

Page 4: ...15H3 2 Handling 96H96H96H12 16H16H16H4 Introduction 97H97H97H13 17H17H17H4 1 Symbol identification 98H98H98H14 18H18H18H4 2 Types article numbers 99H99H99H14 19H19H19H4 3 General description applicati...

Page 5: ...117H32 37H37H37H8 3 Starting exiting TTA Set 118H118H118H32 38H38H38H8 4 Title bar 119H119H119H32 39H39H39H8 5 Overview parameters 120H120H120H34 40H40H40H8 6 Run mode 121H121H121H41 41H41H41H8 7 Prod...

Page 6: ...Contents 6 5662300000 01 08 10...

Page 7: ...Approvals 5662300000 01 08 10 7 1 Approvals 1 1 CE 131H131H131H8 1 2 UL 132H132H132H8 1 3 GL 133H133H133H8 1 4 ATEX 134H134H134H8 1 5 Class 1 Division 2 135H135H135H8...

Page 8: ...ULus 1 3 GL Germanischer Lloyd approval for products 8939670000 and 8939680000 1 4 ATEX Approval according ATEX directive EN 60079 0 and EN 60079 15 for NON Sparking for products 8964310000 und 896432...

Page 9: ...Warrantee statement 5662300000 01 08 10 9 2 Warrantee statement 2 1 36 months warranty 136H136H136H10...

Page 10: ...replace the defec tive one The warranty referred to above covers Weidm ller products Safe where expressively described other wise in writing in this catalogue product description Weidm ller gives no w...

Page 11: ...Notes on Safety 5662300000 01 08 10 11 3 Notes on Safety 3 1 Electrical precautions 137H137H137H12 3 2 Handling 138H138H138H12...

Page 12: ...s including the EMI precautions given in chapter 139H139H139H6 3 2 Handling Check on receipt that the product received corre sponds to the one ordered Unpack the product carefully and ensure the CD Us...

Page 13: ...Introduction 5662300000 01 08 10 13 4 Introduction 4 1 Symbol identification 142H142H142H14 4 2 Types article numbers 143H143H143H14 4 3 General description applications examples 144H144H144H14...

Page 14: ...able signal con verter isolator alarm generator for use in meas urement and control systems In one model a wide variety of input output range and type settings can be configured using a separate CBX10...

Page 15: ...ure millivolts characteristic Isolation of the input signal to the control system This allows the user to use a thermocouple with a grounded hot junction for a quick response at the measurement point...

Page 16: ...Introduction 16 5662300000 01 08 10...

Page 17: ...Operation 5662300000 01 08 10 17 5 Operation 5 1 Status alarm LEDs 145H145H145H18 5 2 Functional block diagram 146H146H146H19 5 3 Specifications 147H147H147H20...

Page 18: ...ulses Table 1 Status indicators Analogue Output status with alarm User may select output value under fault condi tions Output compliant with NAMUR recommendations NE43 can be set 3 6 mA or 21 mA Input...

Page 19: ...Operation 5662300000 01 08 10 19 5 2 Functional block diagram Figure 4 Functional block diagram...

Page 20: ...able between 2 and 102 output Analogue Output DC voltage 0 5 1 5 0 10 2 10 V or span settable between 10 10 V min span 2 5 V DC current 0 20 4 20 0 10 mA or span settable between 0 20 mA min span 5 mA...

Page 21: ...K Thermocouple inputs 0 01 of full scale K CJ error 0 07 C K Step Response Cut off Frequency Settable within 60 ms 1880 ms 1 Hz 3 dB Physical Dimensions 92 4 x 112 5 x 45 mm No of connections 12 Conne...

Page 22: ...Operation 22 5662300000 01 08 10...

Page 23: ...3 6 Installation 6 1 General Competence Warning 148H148H148H24 6 2 Mounting Environmental EMI protection warm up 149H149H149H24 6 3 Marking 150H150H150H25 6 4 Electrical Connections 151H151H151H25 6 5...

Page 24: ...n a weather proof field enclo sure Its atmosphere should be dry well ventilated and dust free Avoid mounting in locations subject to vibration or physical impact The WAVE TTA EX are suitable for EX ap...

Page 25: ...screw clamp or tension clamp type depending on the item article number The connectors are coded to prevent the power supply connector being fitted in the wrong position Test terminals are included to...

Page 26: ...ram Power supply Term No 24 0 V 25 PE 26 24 240 V DC AC Table 4 Power supply Connection diagram Input Resistor RTD Term No IPassive 50 mA IActive 20 mA V 50 V TC V 600 mV 2 Wire 3 Wire 4 Wire Poti Fre...

Page 27: ...am Analogue output Term No 0 20 mA 0 10 V 10 V 10 V 31 TP 32 Out TP 33 Out 41 Out 42 Out Out 43 Out Table 6 Analogue output Connection diagram Digital output relay Term No Alarm 1 Alarm 2 34 N C 35 N...

Page 28: ...Installation 28 5662300000 01 08 10...

Page 29: ...up Configuration 5662300000 01 08 10 29 7 Setup Configuration 7 1 Default setting 153H153H153H30 7 2 CBX100 USB and CBX200 USB introduction 154H154H154H30 7 3 Configuration diagram wiring 155H155H155H...

Page 30: ...Table 8 Default settings 7 2 CBX100 USB and CBX200 USB introduction The CBX100 USB or CBX200 USB is the configura tion interface for the WAVE TTA This is the same interface as can be used for configu...

Page 31: ...scription 156H156H156H32 8 2 Installation 157H157H157H32 8 3 Starting exiting TTA Set 158H158H158H32 8 4 Title bar 159H159H159H32 8 5 Overview parameters 160H160H160H34 8 6 Run mode 161H161H161H41 8 7...

Page 32: ...installed with the file setup exe 8 3 Starting exiting TTA Set Starting TTA Set You can start TTA Set in two different ways 1 Double click on the icon on your computer desktop 2 Click on the Windows S...

Page 33: ...ettings Temperature unit Setpoint Settings from the unit percent Running Values or input units of the trigger level of the digital outputs and the in put unit of the running value indi cation Figure 1...

Page 34: ...7 C S 50 1767 C B 50 1820 C L 200 900 C U 200 600 C User defined RTD RTD type Connection type PT100 PT1000 NI100 NI1000 NI120 Cu10 at 25 C Cu100 at 0 C User defined 2 wire 3 wire 4 wire Resistor Range...

Page 35: ...Out In2 x 0 01 Out In2 5 x 0 001 Input in Output in Output in Output in Output in Output in 0 0 0 0 0 0 10 10 32 3 1 0 3 20 20 45 9 4 2 30 30 55 16 9 5 40 40 63 25 16 10 50 50 71 35 25 18 60 60 77 46...

Page 36: ...Hz 180 ms Response Time Response time is the time between an input step and the output step ADC speed Response time in ms Voltage Current mV Thermo Potentiometer RTD 3 Wire RTD 2 Wire 4 Wire min 140...

Page 37: ...to 100 in put Direct or reverse function Direct action is output increasing as input increases Reverse action is output decreas ing as input increases Direct action is output increasing as input incre...

Page 38: ...0 Input Error If an input or WAVE TTA error occurs the output is set to this value ON The alarm relay is activated after power on Function cir cuit Alarm Relay Normally energised No alarm Alarm Coil o...

Page 39: ...ted when an error is detected Alarm OFF The alarm relay is deactivated when an error is detected Hold The alarm relay hold the actually status None No reaction on an error Table 9 Parameter High Alarm...

Page 40: ...is example the time delay is set for 20 seconds At t1 the measurement exceeds the alarm value but this only lasts for 10 seconds so there is no trip At t2 the measurement again exceeds the alarm trip...

Page 41: ...figuration in the con nected WAVE TTA click on the Read from in strument button Running values Input WAVE TTA input value in percent Output WAVE TTA output value in percent CJC Temperature This the te...

Page 42: ...tware 42 5662300000 01 08 10 A Figure 19 Unit ID A Terminals 8 8 Updates Downloading the latest version The latest version of the TTA Set Software is available from the Weidm ller website at www weidm...

Page 43: ...Testing the product 5662300000 01 08 10 43 9 Testing the product 9 1 Test procedure 164H164H164H44...

Page 44: ...priate input signal source is needed such as Calibrator Portacal 1000 Order No 7940010194 for DC current and Voltage input signals Potentiometer e g 5 k Resistance box Thermocouple source or Millivolt...

Page 45: ...ut Low and Input High 2 Select and set the output signal type required Current or Voltage 3 Select and set the digital outputs as required 4 Click the button Send to Instrument 5 Turn the potentiomete...

Page 46: ...Testing the product 46 5662300000 01 08 10...

Page 47: ...Troubleshooting 5662300000 01 08 10 47 10 Troubleshooting 10 1 Troubleshooting 168H168H168H48...

Page 48: ...the power supply and consider the wiring diagrams and descriptions in chapter 169H169H169H5 and 170H170H170H6 2 Ensure that the input output connections are correct The green Status LED is flashing It...

Page 49: ...Appendix 5662300000 01 08 10 49 Appendix Appendix A Article Overview 174H174H174H50 Index 175H175H175H51...

Page 50: ...cle Overview Modules WAVE TTA WAS6 TTA 8939670000 WAZ6 TTA 8939680000 WAS6 TTA EX 8964310000 WAZ6 TTA EX 8964320000 USB Interface CBX100 USB 7940025031 CBX200 USB 8978580000 Accessory WS 15 5 MC NEUTR...

Page 51: ...ar Language 184H184H184H32 59H59H59HFigure 10 Titlel bar Settings Temperature unit 185H185H185H33 60H60H60HFigure 11 Title bar Settings Setpoint unit 186H186H186H33 61H61H61HFigure 12 Title bar Info 1...

Page 52: ...99H199H21 74H74H74HTable 4 Power supply 200H200H200H26 75H75H75HTable 5 Input 201H201H201H26 76H76H76HTable 6 Analogue output 202H202H202H27 77H77H77HTable 7 Digital output 203H203H203H27 78H78H78HTab...

Page 53: ......

Page 54: ...rface GmbH Co KG Postfach 3030 32720 Detmold Klingenbergstra e 16 32758 Detmold Germany Phone 49 0 5231 14 0 Fax 49 0 5231 14 2083 E Mail info weidmueller com Internet www weidmueller com 165H281H281H...

Reviews: