3 System description of safe I/O modules
| External circuitry of a PN/P output pair
12
1484600000/04/06.2017
u-remote IP20 modules for functional safety manual
3.6 External circuitry of a PN/P output pair
All information in this section refer to the ZVEI position paper
CB24I (Edition 2.0).
The outputs of the module can be circuited as follows.
Options for the external circuitry of the outputs
Circuit diagram Parameterisation
1
2 x single-channel, P-switching
or
dual-channel, P-switching
2
2 x single-channel,
first channel
N-switching
3
dual-channel,
first channel
N-switching
Examples 1 and 2
2 x single-channel, P-switching or dual-channel, P-switching
The outputs in circuit diagram
1
correspond to the type C
source.
1
2
3
4
1
2
3
4
1
2
3
4
DO (PN)
DO (P)
DO (PN)
24 V DC
DO (P)
DO (PN)
DO (P)
1
2
3
External circuitry of the outputs
Test pulse class
Parameterisable per test pulse duration
Test pulse duration
Depending on the parameterisation 0.5 ... 10 ms
Test pulse intervall
200 ms
Rated current
0.5 A (as per EN 61131-2)
Capacitive load
Depending on the parameterisation and the load
current. With test pulses enabled the output current
must be reduced to <10 V within one millisecond.
With test pulses disabled (only possible with V2
modules) the connected capacity must not exceed
250 µF.
Inductive load
As per EN 61131-2 for 0.5 A outputs, maximum
leakage current in state OFF: 100 µA
Lamp load
When using a lamp load the test pulses must be
enabled (V2 modules only).
Example 3
Dual-channel, first channel N-switching
The outputs correspond with the type D source.
1
2
3
4
1
2
3
4
1
2
3
4
DO (PN)
DO (P)
DO (PN)
24 V DC
DO (P)
DO (PN)
DO (P)
1
2
3
External dual-channel circuitry of the outputs
Test pulse class
Parameterisable per test pulse duration
Test pulse duration
Depending on the parameterisation 0.5 ... 10 ms
Test pulse intervall
200 ms
Rated current
0.5 A (as per EN 61131-2)
Capacitive load
Depending on the parameterisation and the load
current. With test pulses enabled the output current
must be reduced to <10 V within one millisecond.
With test pulses disabled (only possible with V2
modules) the connected capacity must not exceed
250 µF.
Inductive load
As per EN 61131-2 for 0.5 A outputs, maximum
leakage current in state OFF: 100 µA
Lamp load
When using a lamp load the test pulses must be
enabled (V2 modules only).
3.7 Operating with and without own test
pulses
All information in this section refer to the ZVEI position paper
CB24I (Edition 2.0).
The parameter settings allow to enable test pulses for the
inputs of the safe I/O modules. These test pulses are gener-
ated and analysed by the module. Thus the highest safety
levels can be achieved (see technical data). The test pulse
duration is determined by the input delay.
When operating without test pulses AUX-O X and AUX-O Y
can be used as outputs for the supply voltage. The active
output signal includes test pulses, the length of which is pa-
rameterisable between 0.5 ms and 10 ms. With V2 modules
these test pulses can be disabled.
Please regard the notes for parameter settings
whenever you disable the test pulses (see module
descriptions in chapter 5).
Summary of Contents for UR20-4DI-4DO-PN-FSOE
Page 1: ...Remote I O system u remote IP20 modules for functional safety Manual Original Letʼs connect ...
Page 8: ...8 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 20: ...20 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 70: ...70 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 72: ...72 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 96: ...96 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 102: ...ANNEX A 6 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 103: ...ANNEX A 7 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 104: ...ANNEX A 8 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 105: ...ANNEX A 9 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 106: ...ANNEX A 10 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 107: ...ANNEX A 11 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 108: ...ANNEX A 12 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 109: ...ANNEX A 13 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 110: ...ANNEX A 14 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 111: ...ANNEX A 15 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 112: ...ANNEX A 16 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 113: ...ANNEX A 17 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 114: ...ANNEX A 18 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 115: ...ANNEX A 19 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 116: ...ANNEX A 20 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 117: ...ANNEX A 21 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 118: ...ANNEX A 22 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 119: ...ANNEX A 23 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 120: ...ANNEX A 24 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 121: ...ANNEX A 25 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 122: ...ANNEX A 26 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...
Page 124: ...A 28 1484600000 04 06 2017 u remote IP20 modules for functional safety manual ...