Installation and Connection
3
UR11 | 3-9
3.4.4 Terminals Recommended for Power Cables
Table 3.5 -
(a) and (b) - Recommended cable lugs for power connections
(a) Cable gauges in mm²
Wire Size
[mm
2
]
Stud
Size
Manufacturer
Ring Lug, P/N
Crimping (installation) Tool P/N
Number of
Crimps
70
M12
Hollingsworth
RM 70-12
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA26L6
Dieless tool: MY29-3 or Y644 or Y81.
Tool + die: Y35 or Y750 / U26RT.
1
120
M12
Hollingsworth
RM120-12
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA28L
Dieless tool: MY29-3 or Y644 or Y81.
Tool + die: Y35 or Y750 / U29RT.
1
150
M12
Hollingsworth
RM150-12
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA30L
Dieless tool: Y644 or Y81.
Tool + die: Y35 or Y750 / U30RT.
1
185
M12
Hollingsworth
RM185-12
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA31L
Dieless tool: Y644 or Y81.
Tool + die: Y35 or Y750 / U31RT.
1
240
M12
Hollingsworth
RM240-12
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA34L6
Dieless tool: Y644 or Y81.
Tool + die: Y35 or Y750 / U34RT.
1
(b) Cable gauges in AWG / kcmil
Wire Size
[AWG/
kcmil]
Stud
Size
Manufacturer
Ring Lug, P/N
Crimping Tool P/N
Number of
Crimps
2/0
M12
Hollingsworth
R 2012
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA26L6
Dieless tool: MY29-3 or Y644 or Y81.
Tool+die: Y35 or Y750 / U26RT.
1
4/0
M12
Hollingsworth
R 4012
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA28L
Dieless tool: MY29-3 or Y644 or Y81.
Tool+die: Y35 or Y750 / U29RT.
1
300
M12
Hollingsworth
R 30012
Hydraulic Tool H6-500.
1
Burndy (FCI)
YA30L
Dieless tool: Y644 or Y81.
Tool+die: Y35 or Y750 / U30RT.
1
350
M12
Hollingsworth
R 35012
Hydraulic Tool: H6-500.
1
Burndy (FCI)
YA31L
Dieless tool: Y644 or Y81.
Tool+die: Y35 or Y750 / U31RT.
1
500
M12
Hollingsworth
R 50012
Hydraulic Tool H6-500.
1
Burndy (FCI)
YA34L6
Dieless tool: Y644 or Y81.
Tool+die: Y35 or Y750 / U34RT.
1
3.4.5 Configurations of the Rectifier
The configuration of the UR11 to operate as 6 pulses and 12 pulses rectifier are presented in this section.
NOTE!
Several additional items are needed for the complete panel assembly, such as: output inverters,
AC fuses, DC link fuses for the output power units protection, circuit breaker or disconnect
switch at the input and in case of 12-pulse configuration is also necessary to provide a phase
shifting transformer.