220 V input connector
Figure 3.16 -
Fans supply terminals: 220 V / 4 A
3.4.6.3 Grounding Connections
ATTENTION!
The neutral conductor of the network must be solidly grounded; however, this conductor must not
be used to ground the rectifier.
ATTENTION!
The rectifier must be obligatorily connected to a protective ground (PE).
Use cables with the recommended gauge indicated in the
. Local standards
should be followed in case different gauges are requested.
The rectifier grounding connection must be connected to the protective ground (PE).
The fastening of the UR11 ground cable connections is done with M12 x 30 bolts (tightening torque: 60 N.m.),
as presented at
Table 3.7 -
Grounding cables
Current (A)
Voltage (V)
Overload
Minimum Cable
Cross-section
Area (mm
2
)
600
380 / 480
ND
240
515
HD
185
470
500 / 600
ND
150
418
HD
120
427
660 / 690
ND
120
340
HD
70