CHAPTER 3 - INSTALLATION AND CONNECTION
23
English
1/U1
4/U2
2/V1
5/V2
6/W2
3/W1
2/V1
5/V2
1/U1
4/U2
6/W2
3/W1
R
S
T
N
PE
R
S
T
N
PE
T
W
V
S
U
R
T
W
V
S
U
R
Figure 3.7
- Soft-Starter SSW-07 with standard connection
DANGER!
The Soft-Starter must be grounded for safety purposes (PE).
The ground connection must comply with the local regulations. Make
the ground connection to a grounding bar or to the general grounding
point (resistance
≤
10 ohms).
DANGER!
The AC input for the Soft-Starter SSW-07 must have a ground
connection.
DANGER!
Do not use the neutral conductor for grounding purpose. Use
dedicated ground conductor.
ATTENTION!
Do not share the ground wiring with other equipment that operate with
high current (for examples: high voltage motors, welding machines,
etc.). When several Soft-Starters SSW-07 are used, observe the
connections in the figure 3.8.
3.2.6 Grounding
Connections
Figure 3.8
- Grounding connections for more than one Soft-Starter SSW-07
3.2.5.1 Standard
Three-Wire
Connection
BARRA DE ATERRAMENTO
INTERNA AO PAINEL
BARRA DE ATERRAMENTO
INTERNA AO PAINEL
GROUNDING BAR
INTERNAL TO THE PANEL
GROUNDING BAR
INTERNAL TO THE PANEL