CHAPTER 3 - INSTALLATION AND CONNECTION
21
English
SSW-07
Model
I²t SCR
(A²s)
FNH aR
Blade Contacts
17 A
720
FNH1-63-K-A
24 A
4000
FNH00-80-K-A
30 A
4000
FNH00-100-K-A
45 A
8000
FNH00-125-K-A
61 A
10500
FNH00-160-K-A
85 A
51200
FNH00-250-K-A
130 A
97000
FNH1-400-K-A
171 A
168000
FNH2-500-K-A
200 A
245000
FNH2-630-K-A
255 A
90000
FNH3-500-K-A
312 A
238000
FNH3-710-K-A
365 A
238000
FNH3-710-K-A
412 A
320000
2 x FNH3-500-K-A
Table 3.8
- I²t of the SCR and aR Weg fuses
Ultra-fast fuses (aR), with l²t smaller than or equal to 75 % of the
value of the SCR indicated (A²s) in table 3.8.
NOTE!
The maximum I²t of the fuse of the SSWs varies according to the
design of the SCR used; therefore, higher rated currents may
present lower I²t.
The fuse rated current should preferably be equal to or higher than
the motor starting current in order to prevent cyclic overloads and
the tripping of the fuse in the prohibited area of the Time x Current
curve.
The proper sizing of the fuse should take into account: the local
standards for electrical installations, the starting cycle, number
of starts per hour, starting current and starting time, ambient
temperature and altitude.
For the correct sizing of the fuses, see WEG Fuse Catalog:
www.weg.net
Automation - Fuses aR and gL/gG - Type NH Blade Contact, NH
Flush End and Diametral.
Annex 1: Sizing Criteria for Ultra-Fast Fuses aR Blade Contact and
Flush End.
Annex 2: Table for aR Fuse Sizing to Protect SSW Soft-Starters
and CFW Inverters.
For the electronic supply protection of the SSW-07 must be used
fuse type D, or circuit breaker type C:
Fuse 2 A Type D or Circuit breakers 2 A Type C.
3.2.4.3 Control
Fuse