10
CFW-10 - QUICK PARAMETER REFERENCE
Parameter
Function
Adjustable Range
Factory
Unit
User Setting Page
Setting
(1)
This parameter can be changed only with the inverter disabled (stopped motor).
Read only
Parameter
Digital Inputs
P263
(1)
Digital Input DI1
0 = No Function
1
-
69
Function
1 = No Function or
P264
(1)
Digital Input DI2
General Enable
5
-
69
Function
2 = General Enable
P265
(1)
Digital Input DI3
3 = JOG
6
-
69
Function
4 = Start/Stop
P266
(1)
Digital Input DI4
5 = Forward/Reverse
4
-
70
Function
6 = Local/Remote
7 = Multispeed
8 = Multispeed using
2
nd
ramp
9 = Forward
10 = Reverse
11 = Forward with 2
nd
ramp
12 = Reverse with 2
nd
ramp
13 =On
14 = Off
15 = Activates 2
nd
ramp
16 = Accelerates E.P.
17 = Decelerates E.P.
18 = Acclerates E.P. with
2
nd
ramp
19 = Decelerates E.P. with
2
nd
ramp
20 = Without external fault
21 = Error reset
Digital Outputs
P277
(1)
Relay Output RL1 function
0 = Fs>Fx
7
-
74
1 = Fe>Fx
2 = Fs=Fe
2 = Is=Ix
4 and 6 = not used
5 = Run
7 = Not Fault
Fx and Ix
P288
Fx Frequency
0.0 to P134
3.0
Hz
75
P290
Ix Current
0.0 to 1.5x1
nom
P295
A
75
Inverter Data
P295
Rated Inverter
1.6
A
75
Current (I
nom
)
2.6
4.0
7.3
P297
(1)
Switching Fraquency
2.5 to 15.0
5.0
kHz
75
DC Braking
P300
DC Braking Time
0.0 to 15.0
0.0
s
76
P301
DC Braking Start frequency
0.0 to 15.0
1.0
Hz
76
P302
Braking Torque
0.0 to 100
50.0
%
76