background image

                                                                                                                                                 

LX3V-4TC 

 

7                                                       

                                                                           

WECON Technology CO., LTD.

 

The  identification  code or  ID  number  for module  is  read from  buffer  memory  BFM  #30  using 

the FROM command. 

 

This number for the LX3V-4TC unit is K2030. 

 

The  PLC  can  use  this  facility  in  its  program  to  identify  the  expansion  module  before 

commencing data transfer from and to the expansion module. 

 

5.

 

System block diagram 

 

 

 

6.

 

Example 

 

In the program shown below, the LX3V-4TC occupies the position of special block number 2 (that is 

the third closest block to the PLC). A Type K thermocouple is used on CH1 and a Type J on CH2. CH3 

and  CH4  are  not  used.  The  averaging  count  is  four.  The  averaged  values  in  degrees  C  of  input 

channels CH1 and CH2 stored respectively in data registers D0 and D3.

 

 

1)

 

Example 1 

This  initial  step  checks  that  the  special  function  block  placed  at  position  2  is  actually  an 

LX3V-4TC,  i.e.  its  unit  identification  number  is  2030  (BFM  #30).  This  step  is  optional,  but  it 
provides a software check that the system has been configured correctly. 

Summary of Contents for LX3V-4TC

Page 1: ...LX3V 4TC User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...

Page 2: ...sted via software control of the LX3V 4TC by use of the TO FROM applied instructions in the PLC LX3V 4TC consumes 5V voltage from LX3V main unit or active extension unit 90mA current of power supply T...

Page 3: ...ronmental specification Item Specification Be sure to use the crimp style terminals that satisfy the dimensional requirements shows in the left figure Apply 0 5 to 0 8 N m 5 to 8 kgf cm torque to tigh...

Page 4: ...r memory area Analog input signal Thermocouple Type K or J either can be used for each channel 4 channels Rated temperature range Type K 100 C to 1200 C Type K 148 F to 2192 F Type J 100 C to 600 C Ty...

Page 5: ...mory BFM Description 0 Thermocouple Type K or J selection mode At shipment H0000 1 4 CH1 to CH4 Averaged temperature reading to be averaged 1 to 4 096 Default 8 5 8 CH1 to CH4 Averaged temperature in...

Page 6: ...of channels used 480ms total conversion time 2 Buffer Memory BFMs 1 to 4 Number of temperature readings to be averaged When the number of temperature readings to be averaged is specified for BFMs 1 to...

Page 7: ...An error can be cleared by writing K0 to BFM 28 using the TO instruction or turning off the power 2 Buffer memory BFM 29 Error states BFM 29 Bit device ON OFF b0 Error When any of b1 to b3 is ON A D c...

Page 8: ...e LX3V 4TC occupies the position of special block number 2 that is the third closest block to the PLC A Type K thermocouple is used on CH1 and a Type J on CH2 CH3 and CH4 are not used The averaging co...

Page 9: ...d output as a bit device in the PLC Y010 in this example Additional Error devices can be output in a similar manner e g b10 BFM 29 Digital range error see example 3 3 Example 3 K4 BFM 1 K4 BFM 2 Numbe...

Page 10: ...exceed 16 and the total system I O is equal or less than 256 I O 3 Ensure that the correct operating range has been selected for the application 4 Check that there is no power overload on either the 5...

Page 11: ...or units Each special block is consecutively numbered from 0 to 15 beginning from the one closest to the base unit A maximum of 16 special blocks can be connected 8 EMC considerations Electromagnetic...

Page 12: ...WECON Technology CO LTD cables away from potential noise sources Additionally it is recommended that signal averaging is used as this will reduce the effects of random noise spikes Version V1 1 0 Dat...

Reviews: