2)

 

The  shielding  wire  cable  shall  be  grounded.  But  their  grounding  point  can  be  the  same  with 

high-voltage lines. 

3)

 

Welding is forbidden at the end of any cable. Ensure the number of connected cables does not 

exceed the designed number of the unit. 

4)

 

Never connect cable with forbidden size. 

5)

 

Fix  the  cable,  so  that  the  stress  does  not  act  on  the  terminal  board  or  the  cable  connection 
area. 

6)

 

The screwing torque of the terminal is from 0.5 to 0.6N.m. Fasten tight to prevent malfunction. 

7)

 

Keep the redundant terminals empty. 

 

5.1 Suitable cable 

Use AWG25-16 to connect the output equipment 
The maximal screwing torque is from 0.5 to 0.6N.m 
The use of different types of cables might cause poor contact between the terminals. It is better to 

use pressed terminals. 

Table 5-1 

Line type 

Cross sectional 

area(mm

2

End-of-pipe treatment 

 

AWG26 

0.1288 

Stranded cable: stripped jacket, rub 

Conductor, then connect the cable. 

Single-core  cable:  stripped  jacket, 
Then connect the cable. 

  ...... 

...... 

AWG16 

1.309 

 

5.2 Output mode 

 

Figure 5-1 

 

 

6.

 

Examples 

 

Summary of Contents for LX3V-2DAV-BD

Page 1: ...LX3V 2DAV BD User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...

Page 2: ...2 When output current make sure that the load resistance should be less than 500 otherwise the output will be lower 3 Please fixed BD module on the PLC poor contact may lead to failure 4 BD module an...

Page 3: ...V 10V 2000 2000 D8116 The digital value of channel 1 10V 10V 2000 2000 D8117 The digital value of channel 2 10V 10V 2000 2000 3 Dimension Table 3 1 LED lights indicating 1 LED1 ON when power ON 2 LED2...

Page 4: ...less than 2K Digital output 12 bit binary Resolution 5mV 10V default scope 1 2000 Precision Full scale 1 A D conversion time 1 scan time The analog digital conversion is completed by the END order Ch...

Page 5: ...6 The screwing torque of the terminal is from 0 5 to 0 6N m Fasten tight to prevent malfunction 7 Keep the redundant terminals empty 5 1 Suitable cable Use AWG25 16 to connect the output equipment The...

Page 6: ...nalog value If the data are not stored into D0 or D2 then D8112 D8113 can be simultaneously used on setting values and other orders such as timer counter 6 2 Examples of Applications Since the LX3V 2D...

Page 7: ...e analog values are stored in D8112 2 Since the data range is converted from A A into 2000 2000 therefore the precision of the analog output is no longer just 5mV Figure 6 1 If the digital range used...

Reviews: