LX3V-2DAV-BD
4
WECON Technology Co., Ltd.
2)
The shielding wire cable shall be grounded. But their grounding point can be the same with
high-voltage lines.
3)
Welding is forbidden at the end of any cable. Ensure the number of connected cables does not
exceed the designed number of the unit.
4)
Never connect cable with forbidden size.
5)
Fix the cable, so that the stress does not act on the terminal board or the cable connection
area.
6)
The screwing torque of the terminal is from 0.5 to 0.6N.m. Fasten tight to prevent malfunction.
7)
Keep the redundant terminals empty.
5.1 Suitable cable
Use AWG25-16 to connect the output equipment
The maximal screwing torque is from 0.5 to 0.6N.m
The use of different types of cables might cause poor contact between the terminals. It is better to
use pressed terminals.
Table 5-1
Line type
Cross sectional
area(mm
2
)
End-of-pipe treatment
AWG26
0.1288
Stranded cable: stripped jacket, rub
Conductor, then connect the cable.
Single-core cable: stripped jacket,
Then connect the cable.
......
......
AWG16
1.309
5.2 Output mode
Figure 5-1
6.
Examples