Wecon LX3V-2DAV-BD User Manual Download Page 2

                                                                                                                                       

LX3V-2DAV-BD

 

1                                                       

                                                                             

WECON Technology Co., Ltd.

 

1.

 

Mounting instruction 

 
Before  the  installation  make  sure  that  the  PLC  host  and  the  equipment  connected  to  BD  module 

have been powered off. Please install the BD module in the corresponding position of the PLC, and 
lock the two standard screws. 

 

Caution 

1)

 

This BD module only support the following  firmware versions or  later. Users can check the PLC 
firmware version in D8001. 

 

LX3VP:25103; 

 

LX3VE: 25201; 

 

LX3V-A2:25014; 

 

LX3V-A1: 22006; 

When mounting module to PLC, all the lights are blinking after power ON PLC please purchase 

new PLC. 

2)

 

When output current, make sure that the load resistance should be less than 500Ω; otherwise 

the output will be lower. 

3)

 

Please fixed BD module on the PLC, poor contact may lead to failure. 

4)

 

BD module and top cover of PLC’s tightening torque is 0.3 ~ 0.6 N.m. 

 

Warning 

Make sure to power off the PLC before mounting or removing the BD module and put the cover in 
right place. 

 

2.

 

Special feature 

 

1)

 

LX3V-2DAV-BD module equips with 2 channels analog output. This module will be mounted in 
the PLC. 

2)

 

The output voltage of LX3V-2DAV-BD module between -10V to 10V, and the digital value will be 

saved in special system address, but the numerical relationship between input and output value 

cannot be changed.   

Table 2-1 

Expansion port 1 (far away from PLC light) 

Address 

Description 

Summary of Contents for LX3V-2DAV-BD

Page 1: ...LX3V 2DAV BD User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...

Page 2: ...2 When output current make sure that the load resistance should be less than 500 otherwise the output will be lower 3 Please fixed BD module on the PLC poor contact may lead to failure 4 BD module an...

Page 3: ...V 10V 2000 2000 D8116 The digital value of channel 1 10V 10V 2000 2000 D8117 The digital value of channel 2 10V 10V 2000 2000 3 Dimension Table 3 1 LED lights indicating 1 LED1 ON when power ON 2 LED2...

Page 4: ...less than 2K Digital output 12 bit binary Resolution 5mV 10V default scope 1 2000 Precision Full scale 1 A D conversion time 1 scan time The analog digital conversion is completed by the END order Ch...

Page 5: ...6 The screwing torque of the terminal is from 0 5 to 0 6N m Fasten tight to prevent malfunction 7 Keep the redundant terminals empty 5 1 Suitable cable Use AWG25 16 to connect the output equipment The...

Page 6: ...nalog value If the data are not stored into D0 or D2 then D8112 D8113 can be simultaneously used on setting values and other orders such as timer counter 6 2 Examples of Applications Since the LX3V 2D...

Page 7: ...e analog values are stored in D8112 2 Since the data range is converted from A A into 2000 2000 therefore the precision of the analog output is no longer just 5mV Figure 6 1 If the digital range used...