Wecon LX3V-2DAV-BD User Manual Download Page 3

                                                                                                                                       

LX3V-2DAV-BD

 

2                                                       

                                                                             

WECON Technology Co., Ltd.

 

M8112 

The flag of switching output mode in CH1 
OFF: Voltage output mode (-10V~10V, -2000~2000) 

ON: 
Disabl

ed   

M8113 

The flag of switching output mode in CH2 

OFF:    Voltage output mode (-10V~10V, -2000~2000) 

D8112 

The digital value of channel 1; (-10V~10V, -2000~2000) 

D8113 

The digital value of channel 2; (-10V~10V, -2000~2000) 

Expansion port 2 (near PLC light) 

Address 

Description 

M8116 

The flag of switching output mode in CH1 
OFF: Voltage output mode (-10V~10V, -2000~2000) 

ON: 
Disable

M8117 

The flag of switching output mode in CH2 

OFF: Voltage out mode (-10V~10V, -2000~2000) 

D8116 

The digital value of channel 1; (-10V~10V, -2000~2000) 

D8117 

The digital value of channel 2; (-10V~10V, -2000~2000) 

 

3.

 

Dimension 

                                                          Table 3-1 

 

 

LED lights indicating 

1)

 

LED1: ON when power ON. 

2)

 

LED2: flashes when communications. 

3)

 

LED3  (AD  1):  On  indicates  enable,  OFF  indicates  disable,  flicker  indicates  exceeding  the 

measurement range. 

4)

 

LED4  (AD  2):  On  indicates  enable,  OFF  indicates  disable,  flicker  indicates  exceeding  the 

measurement range. 

 

If the BD module is plugged into the old firmware version when on the host, all LEDs will be flashing. 

Out-2DAV Output voltage range: -10V~10V 

Vo1+ 

Anode of the channel 1 voltage output 

Vo1- 

Cathode of the channel 1 voltage output 

• 

No connection 

Vo2+ 

Cathode of the channel 2 voltage output 

Vo2- 

Cathode of the channel 2 voltage output 

Summary of Contents for LX3V-2DAV-BD

Page 1: ...LX3V 2DAV BD User manual Website http www we con com cn en Technical Support support we con com cn Skype fcwkkj Phone 86 591 87868869 QQ 1043098682 Technical forum http wecon freeforums net...

Page 2: ...2 When output current make sure that the load resistance should be less than 500 otherwise the output will be lower 3 Please fixed BD module on the PLC poor contact may lead to failure 4 BD module an...

Page 3: ...V 10V 2000 2000 D8116 The digital value of channel 1 10V 10V 2000 2000 D8117 The digital value of channel 2 10V 10V 2000 2000 3 Dimension Table 3 1 LED lights indicating 1 LED1 ON when power ON 2 LED2...

Page 4: ...less than 2K Digital output 12 bit binary Resolution 5mV 10V default scope 1 2000 Precision Full scale 1 A D conversion time 1 scan time The analog digital conversion is completed by the END order Ch...

Page 5: ...6 The screwing torque of the terminal is from 0 5 to 0 6N m Fasten tight to prevent malfunction 7 Keep the redundant terminals empty 5 1 Suitable cable Use AWG25 16 to connect the output equipment The...

Page 6: ...nalog value If the data are not stored into D0 or D2 then D8112 D8113 can be simultaneously used on setting values and other orders such as timer counter 6 2 Examples of Applications Since the LX3V 2D...

Page 7: ...e analog values are stored in D8112 2 Since the data range is converted from A A into 2000 2000 therefore the precision of the analog output is no longer just 5mV Figure 6 1 If the digital range used...

Reviews: