12.0 Troubleshooting Guide
PROBLEM
CAUSES
SOLUTIONS
SmartLine®
controller does not
turn on zone when
expected
Sensor jumper is removed and no
sensor is connected (Sensor LED is
red)
Install jumper wire between SEN terminals
Select OFF mode if desired
Sensor wires have been cut (Sensor
LED is red)
Repair wires
Zone comes on at unexpected time
Program daily start times not set properly or multiple start times set.
Check Program Start Times
Stacked program has commenced
normal operation
Modify settings (such as program start times, zone run times) to prevent
stacking if undesirable
Time of day or date not set properly
Review/set time of day and date
Watering days or omit days/dates not
set properly
Review/set watering days or omit days/dates
Run/Soak feature has extended
watering window
Normal operation to allow water infiltration and prevent runoff
Controller does not operate zone for
expected run time
Pause for Run/Soak in progress. This is normal operation to allow water
infiltration and prevent runoff
Check seasonal % settings if BASIC mode is in use.
Module not installed
Install module
No initial AC power-up of controller
Connect AC power and close control panel