Wiring diagramme 

 

 

 

 

 

 

 

 

 

 

 
 

 

 
 

 

 

 

 

 

 

 

 

11. 

Change the set switching temperature 

 

 

 

The switch-on temperature is factory set at approximately 70°C. This pre-setting is optimal for most 
applications. In the factory setting the resistance value between the measuring points is 730 ohms. 

 
If the switch-on temperature should be changed, so you can do these, when you turn the adjustment screw at the potentiometer. If you turn 

clockwise, the switch on temperature will go down (the resistance will be higher). If you turn counter-clockwise, the switch-on temperature 

will be higher (the resistance will go down). 

 

The temperature range can be adjusted from approximately 67°C to 85°C, deviations from these values can occur by the tolerances of the 

potentiometer. 

Summary of Contents for Duftdos UNPL

Page 1: ...bols 2 2 Saftey 3 2 1 Technical safety advice 3 2 2 Use in accordance with regulations 4 3 Delivery 4 4 Function 4 5 Technical Data 5 6 Fragrance pump 5 6 1 Change the hose set 6 6 2 Sparepartlist per...

Page 2: ...essible at all times 1 4 Further informations For further information please contact your dealer or company WDT Werner Dosiertechnik GmbH Co KG 1 5 Used symbols Danger Warning of Danger Failure to obs...

Page 3: ...y After any repair work have qualified personnel check the safe operation of the unit Use original spare parts only Additional national safety regulations also fully apply to the operation of this uni...

Page 4: ...After you press the push button the dosing is activated for 0 5 seconds till 5 seconds adjustable and aroma is injected into the steam pipe Afterwards the dosing is locked for an adjustable 1 20 minu...

Page 5: ...6 Fragrance pump A peristaltic dosing pump is used for dosing which safely promotes also smallest quantities Even when Air or gas bubbles are trapped in the suction line Rotating rolls press the dosi...

Page 6: ...t persitaltic pump frangrance The peristaltic pump article no Transparent pump cover Sa 14259 Safety disc for roller Sa blue 13633 Hose holder Sa for fragrance with Viton hose 13358 Hose set Sa 2 dosi...

Page 7: ...ommissioning Dosing The dosing unit has to be mounted in an easily accessible place on the wall about 1m above the floor The fragrance canister is placed under the unit The suction hose is inserted in...

Page 8: ...sensor head Then you adjust the desired dosing value at the rotary knob for the dosage The dosing pump delivers per second running time approximately 1 ml fragrance The green LED indicates the unit i...

Page 9: ...suring points is 730 ohms If the switch on temperature should be changed so you can do these when you turn the adjustment screw at the potentiometer If you turn clockwise the switch on temperature wil...

Reviews: