3

WCP85

Installation

(Continued)

furnace drain (if applicable), to the
inlet holes on the pump. Refer to
Figure 5.

STEP 4: INSTALLATION OF
DISCHARGE LINE

NOTE: 

Use 3/8” I.D. (max.) flexible

tubing.. A hose clamp is recommended
(not provided).

A. Extend discharge pipe from barbed

check valve to the highest point
possible. Refer to Figure 6.

B. From this point, direct the

discharge line to the location of the
drainage source. Maintain a
continuous downward slope. 

NOTE:

Construct an inverted  “U” (see

Figure 6) at the highest point of
discharge line if a continuous
downward slope is not possible.
Exercise care not to kink or “pinch off”
the flow of condensate liquid.

STEP 5: INSTALLATION OF
SAFETY SWITCH (IF APPLICABLE)

Connect power cord
to a constant

voltage source. Do not connect to a fan
or other device that may run
intermittently.

A. The pump can be wired directly to

the appliance thermostat to shut
the pump and appliance down in
the event of pump failure. Refer to
Figure 7 for typical wiring diagram.

NOTE:

The alarm can be wired in the

safety switch at the normally open
(“NO”) contact.

TIPS FOR EASY INSTALLATION

1. After reading instructions, check to

make sure installation does not
exceed a maximum of 15 feet of 
vertical lift.

2. Make sure pump is level. No part of

the pump base should be more
than 1/8” off of level plane.

3. Use soapy water on unit when

performing cleaning maintenance.
(Refer to Maintenance guidelines.)

4. For optimum performance, drain

and discharge lines should have a
continuous downward slope. Test
operation of pump to make sure
lines have enough downward slope

Figure 4 - Modification of pipe end to prevent blockage

Figure 5 - Plumbing pipe from drain to inlet holes on pump

Main Drain from Coil

Overflow Drain from
Coil When Required

GFCI
Outlet

Overflow Drain
from Furnace

Condensate Neutralizer
Cartridge (If Required)

Main Drain
from Furnace

High efficiency
gas furnace

Figure 6 - Installation of discharge line

15 Ft.
Max

Inverted “U”

To Main Drain

Hose clamp 

(recommended, not included)

GFCI
Outlet

Do not kink or pinch

3/8” ID Tubing

Summary of Contents for 370100-001

Page 1: ...rials Pump damage could occur if used in these applications and will void warranty Use for clear water application only Safety Guidelines This manual contains information that is very important to kno...

Page 2: ...11 This equipment is only for use on 120 volt single phase and is equipped with an approved 3 con ductor cord and 3 prong grounding type plug as shown in Figure 2 To reduce the risk of electric shock...

Page 3: ...event of pump failure Refer to Figure 7 for typical wiring diagram NOTE The alarm can be wired in the safety switch at the normally open NO contact TIPS FOR EASY INSTALLATION 1 After reading instruct...

Page 4: ...tact Maintenance Make certain that the pump is unplugged before attempting to service or remove any component This pump is assembled in the factory using special equipment therefore only authorized se...

Page 5: ...Refer to Maintenance section for cleaning instructions 1 Refer to Maintenance section for cleaning instructions 2 Measure from bottom of pump to highest point Rework discharge if height is greater tha...

Page 6: ...do not allow limitations on how long an implied warranty lasts or do not allow the exclusions or limitations of incidental or consequential damages so the above limitations might not apply to you Thi...

Page 7: ...OBLEMAS CON EL EQUIPO Para ayudarlo a reconocer esta informaci n observe los siguientes s mbolos Peligro indica una situaci n de riesgo inminente la cual si no se evita provocar la muerte o graves les...

Page 8: ...y la Ley de salud y seguridad ocupacional OSHA Riesgo de choque el ctrico Nunca conecte el cable verde o verde y amarillo a un terminal con corriente 11 Esta bomba es s lo para usar con 120 voltios m...

Page 9: ...a 6 en el punto m s alto de la l nea de descarga si no es posible hacer una pendiente continua hacia abajo Tenga cuidado de no doblar ni apretar el flujo de l quido condensado PASO 5 INSTALACI N DEL I...

Page 10: ...cablear en el interruptor de seguridad al contacto normalmente abierto NO 12 Despu s de la instalaci n pruebe la bomba para asegurarse de que el sistema funcione correctamente 13 Aseg rese de que la i...

Page 11: ...de limpieza 2 Mida desde la parte inferior de la bomba hasta el punto m s alto Ajuste la altura de la descarga si es mayor que 4 57 m 15 pies Consulte el Paso 4 de la Instalaci n para ver las instruc...

Page 12: ...S INDIRECTOS O CONSECUENTES QUEDAN EXCLUIDOS Algunos estados no permiten que se establezcan l mites en la duraci n de las garant as implicitas o no permiten que se excluyan ni se establezcan l mites e...

Reviews: