1. Make sure that the power has been turned OFF at the circuit breaker.
2. Connect wires to the PW flying leads as shown in the
wiring diagram that is appropriate to the electrical supply.
The ground wire (green) must be fastened to ground for
the sensor to work properly.
3. Attach the sensor to the wall box by inserting screws into
the two wide holes on the top and bottom of the attached
metal bracket. Match them up with the holes in the wall box and tighten.
4. Turn the circuit breaker ON. Wait one minute, then push the Auto ON/OFF
switch and the lights will turn ON. There is a delay due to initial power-up of
the sensor that only occurs during installation.
5. Test and adjust the sensor if necessary.
6. Attach the cover plate.
INSTALLATION
WARNING
TURN THE POWER OFF AT THE CIRCUIT BREAKER
BEFORE INSTALLING THE SENSOR OR WORKING ON THE LOAD.
#12 – #14 AWG
Cu Wire Only
Strip Gage
1/2"
12.7mm
Visit our website for FAQs: www.wattstopper.com
Ground
Junction Box
Junction Box
Black (Line)
Red (Load 1)
White (Neutral)
Yellow (Traveler)
PW-103N
PW-103N
120/277V 50/60Hz
White (Neutral)
Black (Line)
Load
1
PW-103N Wiring
Important:
Wire the remote unit to the same branch circuit as the main unit
controlling the load. If relay 2 of the main unit cannot be controlled from the
remote unit, check wiring to be sure both units are on the same branch circuit.
Caution:
Do not install this device if there is not at least 10 meters (30 feet) or
more of wire between the unit and the electrical service panel.