TROUBLESHOOTING

Lights do not turn ON with motion (LED does flash)

1.  Press and release the 

ON/OFF

 button to make sure that the correct lights 

come ON. 

If the lights do NOT turn ON

, check wire connections. 

If the lights 

turn ON

, verify that the correct On Mode is selected in DIP switch 8.

2.  Check to see if light level control is enabled: cover the sensor lens with your 

hand. If the lights come 

ON

, adjust the light level setting. 

3.  If lights still do not turn 

ON

, call 800.879.8585 for technical support.

Lights do not turn ON with motion (LED does not flash)

1.  Press and release the 

ON/OFF

 button to make sure that the correct lights 

come ON. If the lights turn 

ON

, verify that Sensitivity is on High.

2.  Check the wire connections. Verify that connections are tightly secured. 
3.  If lights still do not turn ON, call 800.879.8585 for technical support.

ADJUSTMENTS

Sensor Adjustment

Remove the wall plate. Remove the button cap by firmly squeezing together the 

top sides of the button assembly. Gently pull it away from the unit. 
When the adjustments are completed, replace the button cap by inserting its 

hinges into the tabs on the main unit and then squeeze the top of the button 

while pressing it into the unit. Reinstall the cover plate.

Light Level Adjustment

The light level can be set with loads 

ON

 or 

OFF

. To enable light level control 

and set the threshold: 
1)  Make sure the room is lit appropriately. 
2)  Put the sensor into TEST mode using the Time Delay DIP switches. 
3)  Press and hold the 

ON/OFF

 button for 3 seconds, until you hear a beep. 

4)  Step away from the sensor. After 25 seconds a beep sounds, indicating that 

the threshold level is set. This threshold is retained, even if power is lost, 

until it is re-set or disabled. 

5)  Set the Time Delay DIP switches to the desired delay time.
To disable light level control, press and hold the 

ON/OFF

 button for 

7 seconds

until a double beep tone sounds.

Reset to Default

Use the DIP Switch Settings tables on the previous page to return features 

to factory settings. To reset the PW press and hold the 

ON/OFF

 button

 

for 

10 

seconds

, until a triple beep sounds. This resets the sensor and disables light 

level control (the brightest ambient light will not hold the light 

OFF

).

Summary of Contents for PW-100-24

Page 1: ...C VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec for 10 min with DIP switch setting PIR Adjustment High or Low DIP switch Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual US Patents 6617560 PW 100 24 v3 Passive Infrared Low Voltage Wall Switch Occupancy Sensor Santa Clara CA 95050 800 879 8585 ...

Page 2: ... With the ON Mode DIP switch in the ON position the occupant must press the ON OFF button to turn ON the load The sensor keeps the load ON until no motion is detected for the selected time delay There is a 30 second re trigger delay If occupancy is detected during the delay the sensor turns the load back ON After the re trigger delay elapses the ON OFF button must be pressed to turn ON the load Au...

Page 3: ...ically after ten minutes or when you set a fixed time delay When the Test Mode times out the sensor assumes a 20 minute time delay To restart Test Mode change the time delay setting to any fixed amount and then return it to the Test setting Reduces sensitivity by approximately 50 Useful in cases where the PIR is detecting movement outside of the desired area also consider masking the lens and wher...

Page 4: ...verage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Alerts The PW 100 24 can provide audible and or visible alerts as a warning before the load turns OFF Unit will beep at one minute at 30 seconds and at 10 seconds before turning OFF load When Walk Through is active the unit beeps three times at 10 seconds before the load goes OFF If Visible Alert is also ON the one minute time out ...

Page 5: ...etected Relay Common must be used for proper operation Normally Open N O Closed when occupancy is detected The bottom terminal on the sensor is not used 4 Turn the power on 5 Test and adjust the sensor if necessary 6 Install industry standard decorator wall switch cover plate not included INSTALLATION WARNING TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS OR SENSORS Visit ...

Page 6: ...isabled Enabled Walk Through 9 1 2 3 4 5 6 7 8 Time Delay Walk Through ON ON Mode Not Used Audible Alerts PIR Sensitivity Visible Alerts Test 20 min 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes Service 5 minutes 1 2 3 Time Delay Service bypasses occupancy light level functions Control the load manually using ON OFF button 6 Disabled Enabled Visible Alert Switch 9 is not used Call 800 879...

Page 7: ... from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the button while pressing it into the unit Reinstall the cover plate Light Level Adjustment The light level can be set with loads ON or OFF To enable light level control and set the threshold 1 Make sure the room is lit appropriately 2 Put the ...

Page 8: ...es 1 2 3 If they are all ON the unit is in Service Mode Set the DIP switches to a valid Time Delay setting 2 If re setting the Time Delay switches does not clear the LED call technical support COVER PLATES WattStopper PW series wall switches fit behind industry standard decorator style switch cover plates Cover plates are not included Units come in the following colors which are indicated by the f...

Reviews: