wattstopper PW-100-24 Installation Instructions Manual Download Page 3

Walk-Through 

Mode

(DIP #4 

ON

)

The PW-100-24 turns the load 

OFF

 three minutes after 

the area is initially occupied, if no motion is detected 

after the first 30 seconds. If motion continues beyond 

the first 30 seconds, the set time delay applies.

High 

(DIP #5 

OFF

)

Default setting. Suitable for most applications.

PIR Sensitivity Adjustment

The PW-100-24 constantly monitors the controlled environment and 

automatically adjusts the PIR to avoid common ambient conditions that can 

cause false detections, while providing maximum coverage. 

Fixed Time Delay 

(DIP 1

 ON

, 2 & 3 

OFF

)

Time delays are 5, 10, 15, 

20

 (default), 25, or 30 

minutes.

Test/20 min 

A Test Mode with a short time delay of 5 seconds is 

set when DIP switches 1, 2, & 3 are

 OFF

.  It cancels 

automatically after ten minutes, or when you set a 

fixed time delay. When the Test Mode times out, the 

sensor assumes a 20 minute time delay. To restart 

Test Mode, change the time delay setting to any fixed 

amount and then return it to the Test setting.

Reduces sensitivity by approximately 50%. Useful in 

cases where the PIR is detecting movement outside of 

the desired area (also consider masking the lens) and 

where heat sources cause unnecessary activation.

Low, 50%

(DIP #5 

ON

)

Visit our website for FAQs: www.wattstopper.com

Walk-Through

The Walk-Through mode shortens the time delay to reduce the amount of time 

the load is 

ON

 after a brief moment of occupancy, such as returning to an office 

to pick up a forgotten item then immediately exiting.

No Walk-Through

(DIP #4 

OFF

)

Walk-Through mode disabled.

Time Delays

The PW-100-24 holds the load 

ON

 until no motion is detected for the selected 

time delay. Select the time delay using DIP switch settings. 

Summary of Contents for PW-100-24

Page 1: ...C VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec for 10 min with DIP switch setting PIR Adjustment High or Low DIP switch Light Level Adjustment 8fc to 180 fc Alerts Selectable Audible Visual US Patents 6617560 PW 100 24 v3 Passive Infrared Low Voltage Wall Switch Occupancy Sensor Santa Clara CA 95050 800 879 8585 ...

Page 2: ... With the ON Mode DIP switch in the ON position the occupant must press the ON OFF button to turn ON the load The sensor keeps the load ON until no motion is detected for the selected time delay There is a 30 second re trigger delay If occupancy is detected during the delay the sensor turns the load back ON After the re trigger delay elapses the ON OFF button must be pressed to turn ON the load Au...

Page 3: ...ically after ten minutes or when you set a fixed time delay When the Test Mode times out the sensor assumes a 20 minute time delay To restart Test Mode change the time delay setting to any fixed amount and then return it to the Test setting Reduces sensitivity by approximately 50 Useful in cases where the PIR is detecting movement outside of the desired area also consider masking the lens and wher...

Page 4: ...verage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Alerts The PW 100 24 can provide audible and or visible alerts as a warning before the load turns OFF Unit will beep at one minute at 30 seconds and at 10 seconds before turning OFF load When Walk Through is active the unit beeps three times at 10 seconds before the load goes OFF If Visible Alert is also ON the one minute time out ...

Page 5: ...etected Relay Common must be used for proper operation Normally Open N O Closed when occupancy is detected The bottom terminal on the sensor is not used 4 Turn the power on 5 Test and adjust the sensor if necessary 6 Install industry standard decorator wall switch cover plate not included INSTALLATION WARNING TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE INSTALLING POWER PACKS OR SENSORS Visit ...

Page 6: ...isabled Enabled Walk Through 9 1 2 3 4 5 6 7 8 Time Delay Walk Through ON ON Mode Not Used Audible Alerts PIR Sensitivity Visible Alerts Test 20 min 10 minutes 15 minutes 20 minutes 25 minutes 30 minutes Service 5 minutes 1 2 3 Time Delay Service bypasses occupancy light level functions Control the load manually using ON OFF button 6 Disabled Enabled Visible Alert Switch 9 is not used Call 800 879...

Page 7: ... from the unit When the adjustments are completed replace the button cap by inserting its hinges into the tabs on the main unit and then squeeze the top of the button while pressing it into the unit Reinstall the cover plate Light Level Adjustment The light level can be set with loads ON or OFF To enable light level control and set the threshold 1 Make sure the room is lit appropriately 2 Put the ...

Page 8: ...es 1 2 3 If they are all ON the unit is in Service Mode Set the DIP switches to a valid Time Delay setting 2 If re setting the Time Delay switches does not clear the LED call technical support COVER PLATES WattStopper PW series wall switches fit behind industry standard decorator style switch cover plates Cover plates are not included Units come in the following colors which are indicated by the f...

Reviews: