LOW VOLTAGE WIRING

Open the interior door to access the connectors in the low voltage section. All input/output wiring in this 

section must be low voltage, Class 2 wiring. Do not use the low voltage wiring compartment as a raceway or 

junction box. Refer to local codes regarding Class 2 wiring practices. 

Hardwire Low Voltage Switches (Optional)

LP panels include a switch input for each relay. These accept any of the dry-contact configurations shown 

below. Operation of the switch will turn on/off the corresponding relay.

To control multiple relays from a single input device, we recommend 

using the optional Group Switching Card .  See page 9 .

Figure 9: Low voltage switch and sensor wiring

R  B  Y  W

2-WIRE MAINTAINED
CONTACT

R -to- B JUMPER

B -to- W JUMPER

2-WIRE MOMENTARY
PUSH BUTTON

STANDARD 3-WIRE
MOMENTARY

STANDARD 3-WIRE
MAINTAINED

R  B  Y  W

RED

WHITE

RED

WHITE

BLACK
WHITE
RED

BLACK
WHITE

RED

R  B  Y  W

R  B  Y  W

R  B  Y  W

OCCUPANCY SENSOR or
INDOOR PHOTOCELL

BLACK
BLUE
RED

Blue

Black

Red

White

24VDC

24VR

24V
AC

COMMON

CONTROL

24VDC

R  B  Y  W

COMBINATION OF 
2-WIRE MOMENTARY PUSHBUTTON
WITH OCCUPANCY SENSOR or
INDOOR PHOTOCELL

BLACK
BLUE
RED

Blue

Black

Red

White

24VDC

24VR

24V
AC

COMMON

CONTROL

24VDC

BLACK

WHITE

Black

White

Single relay input 

on panel’s main 

relay switch 

board  

-OR- 

Group channel 

connection 

on Group 

Switching card

R = red: ON 

B = black: OFF 

Y = yellow: Pilot  

W = white: Common

Do not hardwire multiple relay inputs 

together when using a 2-wire momentary 

switch for control . Use a Group Switch Card . 

Visit our web site for FAQs: www .wattstopper .com

Summary of Contents for LP Series

Page 1: ...y 240VAC P115 347 Power Supply 115 or 347VAC Load Ratings 120VAC 50 60Hz 20A Tungsten or Ballast 277 347VAC 50 60Hz 20A Ballast 250VAC 1HP Accessory Power Ouput 800mA 24VDC VAC ACR Environmental Maximum Ambient Temperature 60 C Maximum Humidity 5 to 90 RH non condensing UL cUL Listed for receptacle rated circuit control Installation Wiring Reference ...

Page 2: ...steps 9 CONTENTS SPECIFICATIONS 1 INTRODUCTION 3 Welcome to the LP Series Lighting Control Panels 3 System Wiring Overview 4 INSTALLATION 5 Mount the Enclosure 5 Install Interior 6 CONNECT THE LP8 POWER SUPPLY 7 Power Up and Test Relays 7 Confirm Nominal Operation 7 LOW VOLTAGE WIRING 8 Hardwire Low Voltage Switches Optional 8 Install and Wire Exterior Photocell Optional 9 Using Low Voltage Sensor...

Page 3: ...2 contactors A secure outer cover protects the user from the high voltage area A separate interior enclosure protects the low voltage wiring and components while allowing easy user access to the time clock scheduling controls Most functions are the same for the LP24 as for the LP8 References to LP8 features functions programming and wiring also apply to the LP24 unless specified otherwise If you h...

Page 4: ...24VR 24VAC WHITE RELAY PILOT Manual override switch for relays Factory installed jumper provides 24V rectified power to pilot contacts A different voltage 5 24V can be connected to the YELCOM terminal from other equipment looking to monitor relay state pilot contacts For standard use 3 18 Line Neutral To relay as rquired For standard use 2 18 For pilot use 3 18 Light fixture Light fixture Light fi...

Page 5: ...urdy flat horizontal surface 2 Remove the outer cover by removing the cover screws Set it aside 3 Open the interior door containing the clock keypad and display window by pulling up the two black plastic self retained pop fasteners on the left side 4 Remove the panel interior assembly a Remove the washer and nut that attaches the transformer mounting assembly to the back of the enclosure b Remove ...

Page 6: ...ltage wiring compartments Install Interior Do not reinstall the interior until after the exterior enclosure has been securely mounted to the wall and the conduit wiring holes have been drilled or knocked out 1 Place the interior in the enclosure 2 Align the interior with the studs provided in the enclosure 3 Hold the interior in place while you pull up on the black self retaining pop fasteners to ...

Page 7: ...e voltage terminations of each relay 4 Apply power to the relays 5 Being careful not to touch any line voltage wiring toggle each relay on off again and confirm that each relay con trols the appropriate load Confirm Nominal Operation With power applied to the LP8 panel there should be two 2 green LED indicators glowing on the power supply card in the lower left corner of the panel And there should...

Page 8: ...sensor wiring R B Y W 2 WIRE MAINTAINED CONTACT R to B JUMPER B to W JUMPER 2 WIRE MOMENTARY PUSH BUTTON STANDARD 3 WIRE MOMENTARY STANDARD 3 WIRE MAINTAINED R B Y W RED WHITE RED WHITE BLACK WHITE RED BLACK WHITE RED R B Y W R B Y W R B Y W OCCUPANCY SENSOR or INDOOR PHOTOCELL BLACK BLUE RED Blue Black Red White 24VDC 24VR 24VAC COMMON CONTROL 24VDC R B Y W COMBINATION OF 2 WIRE MOMENTARY PUSHBUT...

Page 9: ...ing card press and hold the Group push button for several seconds The red group LED and the LEDs for relays currently controlled by that input will begin to flash 2 On each Relay Driver card select the relays to be controlled If a relay was previously Smartwired to the group input selected the LED flashes otherwise the LED is off Press the associated Relay Control Button to add delete that relay t...

Page 10: ... can only be overridden OFF during unoccupied periods Remove any LV switching that is landed at the relay input and attempt to turn relay ON using the board override buttons No change in status Go to next step Relay functions normally Verify the LV wiring is not shorted and that the switch is operating correctly Move LV relay connection to a different point on the RD board and attempt to override ...

Page 11: ...o next step Is Daylight Savings set up correctly for the panel s location No make the necessary changes and test again Yes Call tech support 6 I go to enter my on and off times and I get the You are attempting to enter a ON OPEN time that happens after the OFF Close time Please correct before moving on Error message Are you entering ON OFF times using the 24 hour format No Using the 24 hour format...

Page 12: ...A2 Low voltage exterior photocell AS 100 Automatic control switch 120 277VAC 50 60Hz LVS 1 Standard momentary toggle switch RS2 3x Two button low voltage momentary switch L1S Single button low voltage architectural design toggle switch LxS Multi button low voltage architectural design toggle switch DCC2 Low voltage momentary switch Miro Decorator style with LED Multiple options available such as c...

Reviews: