Problem

Test Steps

Next

4

My EM24-A2 

photocell does not 

turn the relay on 

or off.

Is the relay scheduled using the 

“Photocell ON/OFF” or “Photocell and 

Schedule ON/OFF” scenarios?

No – Make the necessary schedule 

changes and test again.
Yes – Go to next step.

Remove the photocell wires or 

connector and jumper from Red to Red.  

Do the relays turn on/off?

Note: If using the “Photocell and 

Schedule ON/OFF” remember to 

adjust the clock time to be within your 

occupied times before doing the jumper. 

No – Call tech Support
Yes – Verify the LV wiring is not 

shorted and that the photocell is 

operating correctly on the roof.

5

The Astronomic 

schedule is turning 

on the relay too 

early/late.

Is the relay scheduled using the 

“Astronomic ON/OFF” or “Astronomic 

and Schedule ON/OFF” scenarios?

No – make the necessary changes 

and test again
Yes – Go to next step

Is the panel’s location set up for the 

correct city/state?

No – make the necessary changes 

and test again
Yes – Go to next step

Is Daylight Savings set up correctly for 

the panel’s location?

No – make the necessary changes 

and test again
Yes – Call tech support

6

I go to enter my 

on and off times 

and I get the “You 

are attempting to 

enter a ON/OPEN 

time that happens 

after the OFF/Close 

time.  Please correct 

before moving on.” 

Error message.

Are you entering ON/OFF times using 

the 24-hour format?

No – Using the 24-hour format 

make the necessary scheduling 

corrections
Yes – Refer to the “Spanning 

Midnight With A Schedule” section 

of the User’s Guide and make the 

necessary scheduling corrections

7

I need to remove 

a sensor from the 

system.

Once a sensor has been connected to 

a relay driver or group switch card low 

voltage input, the input will remain in 

the sensor mode even if the sensor is 

removed.  

 

To restore normal operation:

1.  Remove the sensor wiring from the 

panel input.

2.  Turn the associated relay or group 

off using the red override button 

corresponding to the input where the 

sensor had been connected.

3.  Momentarily jumper the white and 

red terminals. 

4.  Does the relay/group turn on?

No – Call tech support
Yes – Normal operation is restored. 

The input is configured for 

standard low voltage switches.

11

Summary of Contents for LP Series

Page 1: ...y 240VAC P115 347 Power Supply 115 or 347VAC Load Ratings 120VAC 50 60Hz 20A Tungsten or Ballast 277 347VAC 50 60Hz 20A Ballast 250VAC 1HP Accessory Power Ouput 800mA 24VDC VAC ACR Environmental Maximum Ambient Temperature 60 C Maximum Humidity 5 to 90 RH non condensing UL cUL Listed for receptacle rated circuit control Installation Wiring Reference ...

Page 2: ...steps 9 CONTENTS SPECIFICATIONS 1 INTRODUCTION 3 Welcome to the LP Series Lighting Control Panels 3 System Wiring Overview 4 INSTALLATION 5 Mount the Enclosure 5 Install Interior 6 CONNECT THE LP8 POWER SUPPLY 7 Power Up and Test Relays 7 Confirm Nominal Operation 7 LOW VOLTAGE WIRING 8 Hardwire Low Voltage Switches Optional 8 Install and Wire Exterior Photocell Optional 9 Using Low Voltage Sensor...

Page 3: ...2 contactors A secure outer cover protects the user from the high voltage area A separate interior enclosure protects the low voltage wiring and components while allowing easy user access to the time clock scheduling controls Most functions are the same for the LP24 as for the LP8 References to LP8 features functions programming and wiring also apply to the LP24 unless specified otherwise If you h...

Page 4: ...24VR 24VAC WHITE RELAY PILOT Manual override switch for relays Factory installed jumper provides 24V rectified power to pilot contacts A different voltage 5 24V can be connected to the YELCOM terminal from other equipment looking to monitor relay state pilot contacts For standard use 3 18 Line Neutral To relay as rquired For standard use 2 18 For pilot use 3 18 Light fixture Light fixture Light fi...

Page 5: ...urdy flat horizontal surface 2 Remove the outer cover by removing the cover screws Set it aside 3 Open the interior door containing the clock keypad and display window by pulling up the two black plastic self retained pop fasteners on the left side 4 Remove the panel interior assembly a Remove the washer and nut that attaches the transformer mounting assembly to the back of the enclosure b Remove ...

Page 6: ...ltage wiring compartments Install Interior Do not reinstall the interior until after the exterior enclosure has been securely mounted to the wall and the conduit wiring holes have been drilled or knocked out 1 Place the interior in the enclosure 2 Align the interior with the studs provided in the enclosure 3 Hold the interior in place while you pull up on the black self retaining pop fasteners to ...

Page 7: ...e voltage terminations of each relay 4 Apply power to the relays 5 Being careful not to touch any line voltage wiring toggle each relay on off again and confirm that each relay con trols the appropriate load Confirm Nominal Operation With power applied to the LP8 panel there should be two 2 green LED indicators glowing on the power supply card in the lower left corner of the panel And there should...

Page 8: ...sensor wiring R B Y W 2 WIRE MAINTAINED CONTACT R to B JUMPER B to W JUMPER 2 WIRE MOMENTARY PUSH BUTTON STANDARD 3 WIRE MOMENTARY STANDARD 3 WIRE MAINTAINED R B Y W RED WHITE RED WHITE BLACK WHITE RED BLACK WHITE RED R B Y W R B Y W R B Y W OCCUPANCY SENSOR or INDOOR PHOTOCELL BLACK BLUE RED Blue Black Red White 24VDC 24VR 24VAC COMMON CONTROL 24VDC R B Y W COMBINATION OF 2 WIRE MOMENTARY PUSHBUT...

Page 9: ...ing card press and hold the Group push button for several seconds The red group LED and the LEDs for relays currently controlled by that input will begin to flash 2 On each Relay Driver card select the relays to be controlled If a relay was previously Smartwired to the group input selected the LED flashes otherwise the LED is off Press the associated Relay Control Button to add delete that relay t...

Page 10: ... can only be overridden OFF during unoccupied periods Remove any LV switching that is landed at the relay input and attempt to turn relay ON using the board override buttons No change in status Go to next step Relay functions normally Verify the LV wiring is not shorted and that the switch is operating correctly Move LV relay connection to a different point on the RD board and attempt to override ...

Page 11: ...o next step Is Daylight Savings set up correctly for the panel s location No make the necessary changes and test again Yes Call tech support 6 I go to enter my on and off times and I get the You are attempting to enter a ON OPEN time that happens after the OFF Close time Please correct before moving on Error message Are you entering ON OFF times using the 24 hour format No Using the 24 hour format...

Page 12: ...A2 Low voltage exterior photocell AS 100 Automatic control switch 120 277VAC 50 60Hz LVS 1 Standard momentary toggle switch RS2 3x Two button low voltage momentary switch L1S Single button low voltage architectural design toggle switch LxS Multi button low voltage architectural design toggle switch DCC2 Low voltage momentary switch Miro Decorator style with LED Multiple options available such as c...

Reviews: