Call 888 .852 .2778 for Technical Support
#
Problem
Test Steps
Next
4
My EM24-A2
photocell does not
turn the relay on
or off.
Is the relay scheduled using the
“Photocell ON/OFF” or “Photocell and
Schedule ON/OFF” scenarios?
No – Make the necessary schedule
changes and test again.
Yes – Go to next step.
Remove the photocell wires or
connector and jumper from Red to Red.
Do the relays turn on/off?
Note: If using the “Photocell and
Schedule ON/OFF” remember to
adjust the clock time to be within your
occupied times before doing the jumper.
No – Call tech Support
Yes – Verify the LV wiring is not
shorted and that the photocell is
operating correctly on the roof.
5
The Astronomic
schedule is turning
on the relay too
early/late.
Is the relay scheduled using the
“Astronomic ON/OFF” or “Astronomic
and Schedule ON/OFF” scenarios?
No – make the necessary changes
and test again
Yes – Go to next step
Is the panel’s location set up for the
correct city/state?
No – make the necessary changes
and test again
Yes – Go to next step
Is Daylight Savings set up correctly for
the panel’s location?
No – make the necessary changes
and test again
Yes – Call tech support
6
I go to enter my
on and off times
and I get the “You
are attempting to
enter a ON/OPEN
time that happens
after the OFF/Close
time. Please correct
before moving on.”
Error message.
Are you entering ON/OFF times using
the 24-hour format?
No – Using the 24-hour format
make the necessary scheduling
corrections
Yes – Refer to the “Spanning
Midnight With A Schedule” section
of the User’s Guide and make the
necessary scheduling corrections
7
I need to remove
a sensor from the
system.
Once a sensor has been connected to
a relay driver or group switch card low
voltage input, the input will remain in
the sensor mode even if the sensor is
removed.
To restore normal operation:
1. Remove the sensor wiring from the
panel input.
2. Turn the associated relay or group
off using the red override button
corresponding to the input where the
sensor had been connected.
3. Momentarily jumper the white and
red terminals.
4. Does the relay/group turn on?
No – Call tech support
Yes – Normal operation is restored.
The input is configured for
standard low voltage switches.
11