wattstopper LP Series Installation & Wiring Reference Download Page 4

Visit our web site for FAQs: www .wattstopper .com

W

B

Y

R

W

B

Y

R

W

B

Y

R

W

B

Y

R

W

B

Y

R

W

B

Y

R

W

B

Y

R

W

B

Y

R

277V

115V

NEUT

GND

1

2

3

4

5

6

7

8

AS-100

For LP24

models only

Tw

o wir

momentary  switch (typical)

Th

re

e wir

e

momentary  switch (typical)

Ceiling moun

t

Wa

tt Stopper sensor (typical)

4 pole

contactor

*

Din Rail

*

For standa

rd

 use 3/#1

8

For pilot use 4/#1

8

Use 4/#20

Clock Scr

een

Only r

equir

ed if one of the

channel scenarios is

“Photocell On/Of

f”, or

“Photocell and Schedule On/Of

f”.

Optional exterior

photocell EM-24A

2

Gr

oup switch

 

car

d (“GS” Option

)

Inner cover latch (1 of 2). Pull to 

re

lease, pr

ess to latch

.

Gr

ound

Neutral 

Line

 

Relay status LE

D

A

B

C

D

E

F

G

H

Powe

r

supply

ACC. POWER

24VDC 24V

R

24V

AC

WHITE

YELCOM 24V

R

24V

AC

WHITE

RELA

Y PILOT

Manual override switch for r

elays

Factory installed jumper pr

ovides 24V r

ectified power to pilot contacts. 

A dif

fer

ent voltage (5-24V) can be connected to the YELCOM terminal 

fr

om other equipment looking to monitor 

re

lay state pilot contacts.

For standa

rd

 

use 3/#1

8

Line

 

Neutral 

To

 r

elay 

as 

rq

ui

re

d

For standa

rd

 use 2/#1

8

For pilot use 3/#1

8

Light fixtu

re

Light fixtu

re

Light fixtu

re

Notes:

The exterior enclosur

e cover has

a hinged door allowing easy 

access to the low voltage section

 

of the panel. The line voltage 

section is accessible only by 

removing the enclosur

e cover

.

Inside the panel, all low voltage 

terminals ar

e below a hinged 

metal inner cover barrier on 

which the clock scr

een display 

and pr

ogramming keypad 

ar

e mounted

.

HELP

Line

 

Neutral 

Line

 

Neutral 

Line

 

Neutral 

◊ 

Observe corr

ect voltage as marked on power suppl

y.

System Wiring Overview

4

Figure 2: System Wiring Overview

Summary of Contents for LP Series

Page 1: ...y 240VAC P115 347 Power Supply 115 or 347VAC Load Ratings 120VAC 50 60Hz 20A Tungsten or Ballast 277 347VAC 50 60Hz 20A Ballast 250VAC 1HP Accessory Power Ouput 800mA 24VDC VAC ACR Environmental Maximum Ambient Temperature 60 C Maximum Humidity 5 to 90 RH non condensing UL cUL Listed for receptacle rated circuit control Installation Wiring Reference ...

Page 2: ...steps 9 CONTENTS SPECIFICATIONS 1 INTRODUCTION 3 Welcome to the LP Series Lighting Control Panels 3 System Wiring Overview 4 INSTALLATION 5 Mount the Enclosure 5 Install Interior 6 CONNECT THE LP8 POWER SUPPLY 7 Power Up and Test Relays 7 Confirm Nominal Operation 7 LOW VOLTAGE WIRING 8 Hardwire Low Voltage Switches Optional 8 Install and Wire Exterior Photocell Optional 9 Using Low Voltage Sensor...

Page 3: ...2 contactors A secure outer cover protects the user from the high voltage area A separate interior enclosure protects the low voltage wiring and components while allowing easy user access to the time clock scheduling controls Most functions are the same for the LP24 as for the LP8 References to LP8 features functions programming and wiring also apply to the LP24 unless specified otherwise If you h...

Page 4: ...24VR 24VAC WHITE RELAY PILOT Manual override switch for relays Factory installed jumper provides 24V rectified power to pilot contacts A different voltage 5 24V can be connected to the YELCOM terminal from other equipment looking to monitor relay state pilot contacts For standard use 3 18 Line Neutral To relay as rquired For standard use 2 18 For pilot use 3 18 Light fixture Light fixture Light fi...

Page 5: ...urdy flat horizontal surface 2 Remove the outer cover by removing the cover screws Set it aside 3 Open the interior door containing the clock keypad and display window by pulling up the two black plastic self retained pop fasteners on the left side 4 Remove the panel interior assembly a Remove the washer and nut that attaches the transformer mounting assembly to the back of the enclosure b Remove ...

Page 6: ...ltage wiring compartments Install Interior Do not reinstall the interior until after the exterior enclosure has been securely mounted to the wall and the conduit wiring holes have been drilled or knocked out 1 Place the interior in the enclosure 2 Align the interior with the studs provided in the enclosure 3 Hold the interior in place while you pull up on the black self retaining pop fasteners to ...

Page 7: ...e voltage terminations of each relay 4 Apply power to the relays 5 Being careful not to touch any line voltage wiring toggle each relay on off again and confirm that each relay con trols the appropriate load Confirm Nominal Operation With power applied to the LP8 panel there should be two 2 green LED indicators glowing on the power supply card in the lower left corner of the panel And there should...

Page 8: ...sensor wiring R B Y W 2 WIRE MAINTAINED CONTACT R to B JUMPER B to W JUMPER 2 WIRE MOMENTARY PUSH BUTTON STANDARD 3 WIRE MOMENTARY STANDARD 3 WIRE MAINTAINED R B Y W RED WHITE RED WHITE BLACK WHITE RED BLACK WHITE RED R B Y W R B Y W R B Y W OCCUPANCY SENSOR or INDOOR PHOTOCELL BLACK BLUE RED Blue Black Red White 24VDC 24VR 24VAC COMMON CONTROL 24VDC R B Y W COMBINATION OF 2 WIRE MOMENTARY PUSHBUT...

Page 9: ...ing card press and hold the Group push button for several seconds The red group LED and the LEDs for relays currently controlled by that input will begin to flash 2 On each Relay Driver card select the relays to be controlled If a relay was previously Smartwired to the group input selected the LED flashes otherwise the LED is off Press the associated Relay Control Button to add delete that relay t...

Page 10: ... can only be overridden OFF during unoccupied periods Remove any LV switching that is landed at the relay input and attempt to turn relay ON using the board override buttons No change in status Go to next step Relay functions normally Verify the LV wiring is not shorted and that the switch is operating correctly Move LV relay connection to a different point on the RD board and attempt to override ...

Page 11: ...o next step Is Daylight Savings set up correctly for the panel s location No make the necessary changes and test again Yes Call tech support 6 I go to enter my on and off times and I get the You are attempting to enter a ON OPEN time that happens after the OFF Close time Please correct before moving on Error message Are you entering ON OFF times using the 24 hour format No Using the 24 hour format...

Page 12: ...A2 Low voltage exterior photocell AS 100 Automatic control switch 120 277VAC 50 60Hz LVS 1 Standard momentary toggle switch RS2 3x Two button low voltage momentary switch L1S Single button low voltage architectural design toggle switch LxS Multi button low voltage architectural design toggle switch DCC2 Low voltage momentary switch Miro Decorator style with LED Multiple options available such as c...

Reviews: