UNIT DESCRIPTION AND OPERATION

The DSW Dual Technology Multi-Way Wall Switch sensors combine advanced 

passive infrared (PIR) and ultrasonic technologies into one unit. The combined 

technologies help to eliminate false triggering even in difficult applications. 
Selectable operating modes allow the sensor to turn a load 

ON

, and hold it 

ON

 

as long as either or both technologies detect occupancy. It allows for up to 4 

sensors to be connected to the same circuit. The first sensor to detect occupancy 

will turn 

ON

 all the lights that are connected to the same circuit. After the room 

is unoccupied, the last sensor that detected occupancy turns 

OFF

 all the lights 

once the time delay has expired. The occupant can turn 

OFF

 the load at any time 

by pressing the 

ON/OFF

 button of any sensor that is connected to the circuit. 

A “walk-through” mode can turn lights off after only 3 minutes if no activity is 

detected after 30 seconds following an occupancy detection.
The DSW-301 has one relay and one 

ON/OFF

 button. The DSW-302 contains two 

relays and two 

ON/OFF

 buttons to allow control of one or two loads independently. 

Pressing a button toggles the state of the corresponding relay. Optional Neutral is 

also available on all models.
DSW sensors contain a light level sensor. If adequate daylight is present, the 

sensor holds the load 

OFF

 until light levels drop, even if the area is occupied. In 

the DSW-302, light level only affects the load on Relay 2. Users can override this 

function by pressing the 

ON/OFF

 button. See the 

Light Level Adjustment

 section.

Turning Load(s) ON (ON Mode)

The relays are programmed independently for either 

Auto ON 

or 

Manual ON

. In 

either mode, the load can be turned 

ON

 or 

OFF

 using the 

ON/OFF

 button.

Manual ON

DIP 8 

ON

 for Relay 1

DIP 9 

ON

 for Relay 2

With an 

ON Mode

 DIP switch in the 

ON

 position, the 

occupant must press the 

ON/OFF

 button to turn 

ON

 the load. The sensor keeps the load 

ON

 until no 

motion is detected for the selected time delay. There 

is a 30 second re-retrigger delay. If occupancy is 

detected during the delay, the sensor turns the load 

back 

ON

. After the re-trigger delay elapses the 

ON/

OFF

 button must be pressed to turn 

ON

 the load.

Auto ON 

DIP 8 

OFF

 for Relay 1

DIP 9 

OFF

 for Relay 2

With an 

ON Mode

 DIP switch in the 

OFF

 position, 

the load turns 

ON

 and 

OFF

 automatically based 

on occupancy. If the load is turned 

OFF

 manually, 

Presentation Mode operation applies. This prevents 

the load from turning 

ON

 automatically after it was 

deliberately turned 

OFF

. Pressing the button to turn 

lights 

ON

 returns the sensor to 

Auto ON

 mode.

Summary of Contents for DSW-301

Page 1: ...347 VAC 1500 W ballast LED 1 4 HP Load Limits for relay 2 120 VAC 800 W tungsten ballast E ballast LED 1 6 HP 277 VAC 1200 W ballast E ballast LED 1 6 HP 347 VAC 1500 W ballast LED 1 6 HP Time Delay...

Page 2: ...responding relay Optional Neutral is also available on all models DSW sensors contain a light level sensor If adequate daylight is present the sensor holds the load OFF until light levels drop even if...

Page 3: ...SETTINGS for more information Test 20 min DIP 1 2 OFF A Test Mode with a short time delay of five seconds is set when DIP switches 1 2 are OFF It cancels automatically after ten minutes or when you s...

Page 4: ...No audible warnings provided Trigger Mode The DSW sensor has four occupancy trigger options set with DIP switches 5 and 6 Determine the appropriate option using the Trigger matrix In the Trigger Mode...

Page 5: ...sensitivity can be adjusted using the trimpot under the ON OFF buttons PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Ultrasonic Coverage 10 3 0m 7 5 2 2m 13 4 0m 10 3 0m Ma...

Page 6: ...will not hold the light OFF INSTALLATION WARNING TURN OFF THE POWER AT THE CIRCUIT BREAKER BEFORE INSTALLING THE SENOR WORKING ON THE LOAD 1 Make sure that the power has been turned OFF at the circui...

Page 7: ...away tab 8 flying leads for line load ground and multi way connections DSW 302 shown The DSW 301 does not include these two leads Yellow Red Green Black Brown Blue Neutral Optional Wiring MULTI WAY Th...

Page 8: ...utral Neutral optional Line Yellow Red Primary Load Brown Secondary Load Neutral optional Ground Green Ground Green Red Brown Blue Blue Bi level Wiring DSW 302 or DSW 302 347 up to 4 sensors Note Butt...

Page 9: ...a 30 second re trigger delay for the sensor set in Manual ON mode or instant re trigger for the sensor set in Auto ON mode After the re trigger delay elapses the ON OFF button of the sensor set in Man...

Page 10: ...ancy Re trigger seconds duration Option C Both Both Both 5 Standard Either 5 Either Option A Either Either 5 PIR Both Option B PIR PIR PIR 5 3 Disabled Enabled Walk Through Trigger Mode DSW 302 ONLY O...

Page 11: ...support Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operation set DIP switch 1 to ON then reset switches 1 and 2 to OFF to st...

Page 12: ...al damages arising out of or in connection with the use or performance of this product or other indirect damages with respect to loss of property revenue or profit or cost of removal installation or r...