Call 800.879.8585 for Technical Support
Load
Red
Black
Neutral
Line
Green
Neutral
(optional)
Ground
Yellow
DSW-301 and DSW-301-347 Wiring
Red
Black
Neutral
Line
Green
Ground
Blue
Primary
Load
Secondary
Load
Neutral
(optional)
Brown
Yellow
Red
Black
Neutral
Line 1
Green
Ground
Blue
Primary
Load
Brown
Secondary
Load
Line 2
Neutral
Neutral
(optional)
Yellow
DSW-302 and DSW-302-347
Bi-Level Wiring
DSW-302 and DSW-302-347
Dual Circuit Wiring
OPTIONAL NEUTRAL WIRING
For applications requiring neutral
wiring, remove tab as shown to expose
terminals for wiring.
Breakaway
tab
Optional neutral
terminals behind
breakaway tab
8" flying leads for
line, load, ground
and multi-way
connections
DSW-302 shown.
The DSW-301 does
not include these
two leads
Yellow
Red
Green
Black
Brown
Blue
Neutral Optional Wiring
MULTI-WAY
The Multi-Way capability is available on all models. Sensors can easily be wired
together for convenient control of a common load. When wiring this way, only use
300 series sensors. Multi-Way in 300 series is not compatible with prior sensor
models.
The following princlples apply for Multi-Way:
All units can see each other’s push button events and respond accordingly.
All units can see each other’s PIR trigger event. The response will be determined
by the Light Level setting and/or conditions of the space of the detecting sensor.
The time delay for all units is defined by the unit with the smallest time delay.