3.4 Commercial cabinet installation
Choice of installation position
3.4.1 Installation preparation
Minimum 500mm open space
Minimum
2000mm
open space
Minimum
2000mm
open space
Minimum
2000mm
open space
Pre-installation check
Before proceeding with the installation, pre-check the battery to make sure it is safe.
Use a digital multimeter to measure the voltage between the positive terminal (+) and the negative terminal (-) of the
battery module.
The standard voltage shall be between 30V and 43.8V.
Test Procedure:
Set the multimeter to the DC voltage, connect the red meter to the positive terminal and the black meter to the negative
terminal.
Recommended installation space of single rack / multiple racks:
30-43.8
V
Negative Terminal
Positive Terminal