4. Inputs / Outputs

4.1 Power Supply

4.2 Heating/cooling Input

Purpose: 
This input allows switching the regulation mode for the system: Heating or cooling.
Source of the signal:
    • A mechanical switch
    • The Heat Pump
    •  A BT-WR02 paired on the BT-CT02 central unit as an ON/OFF device. This solution allows 

getting a remote control of the H&C mode from the application.

Format of the signal:
The input could be free contact or live contact 230V.

The H&C mode is then propagate over all the system.
Only one device is the system should be able to select the H&C mode (Master H&C device). Other possible H&C switch signal 
sources:
 

• BT-CT02 RF Central unit.

 

• H&C input on WFC-03 HC RF  controllers.

 

• Digital thermostat configured as a Master H&C thermostat in manual or automatic mode.

The DIP switch on the WFC-03 HC RF controllers allows to select the device in charge of the H&C mode (Master H&C device).

The time before H&C switch is defined by the DIP2 (See 3.3):
 

• DIP2 = OFF. 2 seconds.

 

• DIP2 = ON. 5 minutes.

Mode

Free contact

Live contact

Heating

Opened

No signal

Cooling

Closed

230Vac

Power

supply

Junction 
earth

Summary of Contents for WFC-03 HCM RF 230

Page 1: ...wattswater fr WFC 03 HCM RF 230 Water Floor Heating and Cooling module Installation manual...

Page 2: ...PRODUCT DESCRIPTION 4 LED color meanings 4 Push button 4 DIP switch configuration 4 INPUTS OUTPUTS 5 Power Supply 5 Heating cooling Input 5 Pump Output 6 Humidity detection input 6 Dehumidifier output...

Page 3: ...tion complies with existing regulations before operation to ensure proper use of the installation 2 Presentation The WFC 03 HCM RF 230 is especially designed to control heating and cooling in combinat...

Page 4: ...Error Led Red Blue Green Red blinking NTC error Blue blinking Global humidity detection In that case the dehumidifier is triggered Fix Green Pump is triggered Green Blue blinking Global humidity detec...

Page 5: ...mode is then propagate over all the system Only one device is the system should be able to select the H C mode Master H C device Other possible H C switch signal sources BT CT02 RF Central unit H C in...

Page 6: ...4 4 When the WFC 03 HC RF controller orders the dehumidifier 4 4 Humidity detection input When DIP1 ON See 3 3 the product manages a humidity detection input with 2 possible types of signal depending...

Page 7: ...ll the time 4 7 External antenna The distance between 2 devices with internal antenna should be at least 50cm The controller embeds an internal antenna If require an external antenna can be connected...

Page 8: ...lave device mode All LEDs are blinking green When link is completed WFC 03 HC RF returns to the RF pairing menu and WFC 03 HCM RF 230 returns to normal mode 5 System configuration The WFC 03 HCM RF 23...

Page 9: ...WFC 03 HCM RF 230 improves the RF communication Usage of a repeater paired to the WFC 03 HC RF may be required Red blinking on Pump Humidity Led NTC error If DIP4 ON a water temperature sensor should...

Page 10: ...ctromagnetic disturbance 2014 30 UE Restriction of the use of certain hazardous substances Directive RoHS 2011 65 EU Directive on the restriction of the use of certain hazardous substances in electric...

Page 11: ...ation sheet are supplied by way of information only and are not binding Watts Industries reserves the right to carry out any technical and design improvements to its products without prior notice Warr...

Reviews: