10

The heating setpoint can be set from 40 to 95°F (4.5 to 35°C). The Heat On symbol is shown 
on the display when the thermostat is heating. Heating for freeze protection is provided 
whenever the air or floor temperature falls below 40°F (4.5°C), regardless of operating mode.

Regular Heating

W1 relay is on when the air temperature falls 1.5°F (1°C) below the Heat To setting. 
When the temperature reaches the Heat To setting, the relay turns off. 

Radiant Floor Heating

When Radiant Floor Heating is selected in the setup menu, the W1 relay operates using 
Pulse Width Modulation. This improves comfort for radiant systems with high mass floors. 
• 100% on time at Heat To setting -1.5°F 
• 50% on time at Heat To setting
• 0% on time at Heat To s 1.5°F

Room Sensor and Averaging

The thermostat can measure room temperature between -46 to 212°F (-43 to 100°C). 
The room temperature can be measured using a combination of the built-in and 
auxiliary sensors.
• Built-in room sensor only
• Built-in room sensor with auxiliary room sensor(s) (temperature is averaged)
• Auxiliary room sensor only

Floor Sensor for Radiant Floor Heating

The thermostat can measure floor temperature between -46 to 212°F (-43 to 100°C). 
If a floor sensor is connected, floor minimum and maximum settings are available. 
The floor heating setpoint is adjustable from 40 to 100°F (4.5 to 38.0°C).
For a combination of air and floor temperature control, leave the internal air sensor on 
in the setup menu. A floor minimum can be used to prevent a fast drop in temperature 
caused by receding solar exposure. This operation is recommended for areas heated 
by afternoon sun through large windows. When the sun sets, it can take a long time 
for the floors to get warm again. This may cause the room to cool off too much in the 
early evening. A floor minimum setting can help with this condition by maintaining a 
floor minimum temperature. Keep in mind the floor minimum temperature will override 
the air temperature, and if set too high, may overheat the room.
A floor maximum is recommended for rooms with hardwood floors. Setting floor 
minimum and maximum temperatures is a way of enhancing the comfort of the living 
space while protecting floor coverings.
If there are more than one floor temperature sensors, the temperature is averaged.

Warm Weather Shut Down (WWSD)

The heating system can automatically shut off based upon the outdoor temperature 
and the WWSD setting. This provides a convenient way to shut off radiant floor heating.

Sequence of Operation

Heating Operation

Summary of Contents for W561

Page 1: ...Please read carefully before proceeding with installation Your failure to follow any attached instructions or operating parameters may lead to the product s failure Keep this Manual for future refere...

Page 2: ...r Settings 12 Away 12 Schedule 12 Display 13 Time 14 WiFi 15 WiFi and Connectivity Troubleshooting 16 Installer Settings 17 Setup 17 Setup Toolbox 17 Setup Temp 18 Setup Sensors 19 Setup Alerts 19 Set...

Page 3: ...r moderate injury This symbol identifies practices actions or failure to act which could result in property damage or damage to the equipment Read Manual and all product labels BEFORE using the equipm...

Page 4: ...condensing environment No exposure to extreme temperatures beyond 32 122 F 0 50 C No draft direct sun or other cause for inaccurate temperature readings Away from equipment appliances or other source...

Page 5: ...ng worked on turned off Please be aware local codes may require this thermostat to be installed or connected by an electrician Thermostat Front Thermostat Base Stud Switch Box 3 1 4 83 mm While holdin...

Page 6: ...ntrol 304V or 306V B1 BP PS V1 T1 ZVC1 ZVC1 The W561 WiFi Thermostat operates a radiant floor heating system The thermostat uses the built in air temperature sensor W561 WiFi Thermostat C R RH1 W1 AWA...

Page 7: ...304V or 306V ZVC1 B1 BP PS V1 S1 T1 ZVC1 The W561 WiFi Thermostat operates a radiant floor heating system based upon the floor temperature sensor included The built in air sensor is disabled W561 WiFi...

Page 8: ...uilt in and or external B1 BP PS V1 S1 S2 T1 ZVC1 Legend ZVC1 W561 WiFi Thermostat C R RH1 W1 AWAY S1 S2 SEN COM Zone Valve Control or Switching Relay C R AWAY W B1 Boiler BP Boiler Pump PS System Pum...

Page 9: ...and or external B1 BP PS V1 S1 T1 ZVC1 ZVC1 W561 WiFi Thermostat C R RH1 W1 AWAY S1 S2 SEN COM Zone Valve Control or Switching Relay C R AWAY W Legend B1 Boiler BP Boiler Pump PS System Pump T1 W561...

Page 10: ...12 F 43 to 100 C If a floor sensor is connected floor minimum and maximum settings are available The floor heating setpoint is adjustable from 40 to 100 F 4 5 to 38 0 C For a combination of air and fl...

Page 11: ...re to the current schedule event Go to settings Swipe to view Weather Outdoor temperature Floor temperature Heat To setting Go to schedule After 60 seconds of inactivity the thermostat home screen dis...

Page 12: ...le Mon Tue Wed Thu Fri Info Set heating temperature Select skip if you don t want a temperature change Set schedule start time On Skip Wake Schedule Setup Mon Tue Wed Thu Fri 6 00 AM Heat to 70 Operat...

Page 13: ...30 to 100 100 BRIGHTNESS INACTIVE Select the brightness when not in use Off 30 to 100 50 BACKGROUND Select the background color Light Blue Night Latte Espresso Blue LANGUAGE Select the language Engli...

Page 14: ...nd Eastern DAYLIGHT SAVING TIME Select the brightness when not in use Off On On When connected to the Internet the time can be set automatically The time and date can be manually set by highlighting a...

Page 15: ...rms of Use available at https www watts com terms of use by pressing AGREE below Ifyoudonotaccepttheseterms this product can still be used without WiFi features WIFI NEXT Off On Time Source NEXT Autom...

Page 16: ...net Service Provider ISP for assistance with router setup with these configurations The router must provide a 2 4 GHz signal The thermostat is not compatible with 5 GHz networks The router is using WP...

Page 17: ...een user and installer access levels User access level restricts access in the Setup Menu User Installer Installer STATUS The current status of warm weather shut down cold weather shut down and each o...

Page 18: ...floor and an air sensor Off 40 to 95 F Off 4 5 to 35 0 C Off FLOOR MIN AWAY Select the floor temperature while in away Applies when there is both a floor and an air sensor Off 40 to 95 F Off 4 5 to 35...

Page 19: ...d Com wiring terminals Off Room Floor Outdoor Off INTERNAL ROOM SENSOR Select if the internal room temperature sensor is on or off Only available when Sensor 1 or 2 is set to read a room or floor sens...

Page 20: ...ure has been set Check the auxiliary sensor wire for short circuits according to the sensor in stallation manual It may be necessary to replace the auxiliary sensor Once the error has been corrected t...

Page 21: ...mm Enclosure White PVC plastic NEMA Type 1 Approvals Meets Class B ICES FCC Part 15 Ambient conditions Indoor use only 32 to 122 F 0 to 50 C RH 90 non condensing Power supply 15 to 30 V ac dc 2 VA sta...

Page 22: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 23: ..._ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _...

Page 24: ...le visitors on the job site or damage caused as a result of post installation work This Limited Warranty shall be invalidated by any abuse misuse misapplication or improper installation of the Product...

Reviews: