Master Programming Mode SXT
(continued)
14. Current Day (Display Code CD)
Press the Extra Cycle button . Use this display to set the current day
on systems that have been configured as Day of Week controls .
This setting is identified by "CD" in the upper left-hand corner of the
screen . Use the Up and Down buttons to select from Day 1 through
Day 7 .
Figure 25
15. Flow Meter Type (Display Code FM)
Press the Extra Cycle button . Use this display to set the type of flow
meter connected to the control . This option setting is identified by
"FM" in the upper left-hand corner of the screen . Use the Up and
Down buttons to select one of the 8 available settings .
Abbreviation
Description
P0.7
3/4" Paddle Wheel Meter
t0.7
3/4" Turbine Meter
P1.0
1" Paddle Wheel Meter
t1.0
1" Turbine Meter
P1.5
1.5" Paddle Wheel Meter
t1.5
1.5" Turbine Meter
P2.0
2" Paddle Wheel Meter
Gen
Generic or Other non-Fleck Meter
Figure 26
16. Meter Pulse Setting (Display Code K)
Press the Extra Cycle button . Use this display to specify the meter
pulse setting for a non-standard flow meter . This option setting is
identified by "K" in the upper left-hand corner of the screen . Use the
Up and Down buttons to enter the meter constant in pulses per unit
volume .
Figure 27
17. End of Master Programming Mode
Press the Extra Cycle button to save all settings and exit Master
Programming Mode .
W110 LXT Downflow Softeners and SXT Filters
18