Modulating Boilers (Terminals 4 to 11)

The control provides either a 0-10 V (dc) or a 4-20 mA output to each boiler . Polarity is important .
•  Connect the control Mod (+) terminals 4, 6, 8, 10 to boilers 5, 6, 7 and 8 analog signal input (+) 

respectively .

•  Connect the control Mod (-) terminals 5, 7, 9, 11 to boilers 5, 6, 7 and 8 analog signal input (-) 

respectively .

Some modulating boilers may also require a boiler on/off enable signal in addition to the 

modulating signal. Please consult the boiler manual.

Modutrol IV

tekmar

B
R

W

+

-

tekmar

V9055

+

-

B
R

W

Modutrol IV™

0 - 135 

Ω

 

 

Actuating

Motor

B

R

W

Mod

+
-

Modutrol IV

tekmar

B
R

W

+

-

tekmar

V9055

+

-

B
R

W

B

R

W

V9055™

0 - 135 

Ω

Actuating

Motor

Mod

+
-

The 4 to 20 mA output can be converted to a 0 - 135 Ω 

output for a Modutrol IV™ gas valve actuating motor using a 

0 - 135 Ω tekmar Converter 005 (sold separately) .

The 4 to 20 mA output can be converted to a 0 - 135 Ω 

output for a V9055™ gas valve actuating motor using a 

0 - 135 Ω tekmar Converter 005 (sold separately) .

Boiler 

Control 

294

Boiler 

Control 

294

Modutrol IV™ and V9055™ are trademarks of Honeywell, Inc .

Boiler Enable (Terminals 12 to 19)

A single stage condensing or non-condensing boiler is enabled through the TT contacts .
•  For Boiler 5 connect the Boiler Enable terminals 12 and 13 to the boiler TT contacts .
•  For Boiler 6 connect the Boiler Enable terminals 14 and 15 to the boiler TT contacts .
•  For Boiler 7 connect the Boiler Enable terminals 16 and 17 to the boiler TT contacts .
•  For Boiler 8 connect the Boiler Enable terminals 18 and 19 to the boiler TT contacts .

Boiler Expansion (Terminals 1, 2, 3)

The control operates 4 on board boilers and is expandable in groups of 4 up to a  

maximum of 16 through the use of boiler expansions . The control connects to the 

expansion through a wired three-wire connection . The maximum bus cable length is 

100 feet (30 m) using 18 AWG solid conductor cable .
•  Connect the 294 terminal 18 (-) to the 294EXP terminal 1 (-) .
•  Connect the 294 terminal 19 (+) to the 294EXP terminal 2 (+) .
•  Connect the 294 terminal 20 (Gnd) to the 294EXP terminal 3 (Gnd) .

18 19 20

Gnd

-

+

Expansion

1

2

3

Gnd

-

+

Expansion

This section explains how to wire individual devices to the Smart Boiler Expansion 294EXP .

Wiring Instructions

Summary of Contents for tekmar 294EXP

Page 1: ...t Boiler Expansion 294EXP IOM T 294EXP WARNING Please read carefully before proceeding with installation Your failure to follow any attached instructions or operating parameters may lead to the produc...

Page 2: ...ion 5 Wiring Schematic 6 Wiring Instructions 7 User Interface 9 Status Icons 9 Labels for Boilers 9 to 12 or 13 to 16 9 Sequence of Operation 10 DIP Switches 10 Power On LED 10 Communication LED 10 Bo...

Page 3: ...re are no user serviceable parts inside the control Attempting to do so voids warranty To avoid serious personal injury and damage to the equipment It is your responsibility to ensure that this contro...

Page 4: ...nada license exempt RSS standard s Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received includi...

Page 5: ...o fasten the two bottom screws When choosing the location for the control consider the following Keep dry Avoid potential leakage onto the control RH 90 to 104 F 40 C Non condensing environment Do not...

Page 6: ...ture 32 F to 122 F 0 C to 50 C Use Copper Conductors Only H2062B 7 6 Boiler 6 5 4 Boiler 5 Mod 9 8 Boiler 7 11 10 Boiler 8 13 12 Boiler 5 Enable 15 14 Boiler 6 Enable 17 16 Boiler 7 Enable 19 18 Boile...

Page 7: ...trol 294 Boiler Control 294 Modutrol IV and V9055 are trademarks of Honeywell Inc Boiler Enable Terminals 12 to 19 A single stage condensing or non condensing boiler is enabled through the TT contacts...

Page 8: ...L L N G Ground Boiler 1 20 21 Pump Valve C R R C Boiler 1 20 21 Pump Valve For 120 V ac valves Connect the power source line wire L to terminal 20 Connect a wire from terminal 21 to the valve Line In...

Page 9: ...uire les risques d lectrocution choc ne pas raccorder un circuit fonctionnant plus de 150 V la terre L 2 3 1 Gnd Expansion Expansion 5 to 8 Set switches 1 to Off 2 to Off Mod Mod Mod Smart Boiler Expa...

Page 10: ...closed Off Boiler enable 6 10 14 relay is open Boiler 7 11 15 On Boiler enable 7 11 15 relay is closed Off Boiler enable 7 11 15 relay is open Boiler 8 12 16 On Boiler enable 8 12 16 relay is closed...

Page 11: ...LED Off Check that the boiler expansion on wiring terminals 1 2 and 3 are connected using 3 conductor 18 AWG LVT wire if connections are less than 100 feet 30 m Connections exceeding 100 feet 30 m or...

Page 12: ...of any kind or nature which arise out of or are related to any such representations or warranties by Purchaser to its customers The pass through Limited Warranty does not apply if the returned Product...

Reviews: