Symptom
Description
Power LED Off
Using an electrical meter, check that the supply voltage is between 103 .5 and 126 .5 V (ac) . If the supply voltage
is correct and the Power LED remains off the control may be faulty .
Communication LED
Off
Check that the boiler expansion on wiring terminals 1, 2, and 3 are connected using 3-conductor 18 AWG LVT
wire if connections are less than 100 feet (30 m) . Connections exceeding 100 feet (30 m) or installed in high
radio-frequency environments should use 3-conductor, 22 AWG shielded-twisted pair . The boiler expansion
wiring is polarity sensitive so it is important to check that the wire color codes are in the correct terminal locations .
Troubleshooting