27
MOTOR TROUBLE SHOOTING CHART
TROUBLE
CAUSE
WHAT TO DO
Motor fails to start
Blown fuses
Replace fuses with proper type and rating.
Overload trips
Check and rest overload in starter.
Improper power supply
Check to see that power supplied agrees with motor nameplate and load factor.
Open circuit in winding or control switch
Indicated by humming sound when switch is closed.
Mechanical failure
Check to see if motor and drive turn freely.
Check bearing and lubrication.
Short circuited stator
Indicated by blown fuses. Motor must be rewound.
Poor stator coil connection
Remove end bells, locate with test lamp.
Rotor defective
Look for broken bars or end ring.
Motor may be overloaded
Reduce load.
Motor Stalls
One phase connection
Check lines for open phase.
Wrong application
Change type or size. Consult manufacturer.
Overload motor
Reduce load.
Low motor voltage
See that nameplate voltage is maintained.
Check connection.
Open circuit
Fuses blown, check overload relay, stator and push buttons.
Motor runs and then dies down
Power failure
Check for loose connections to line, to fuses and to control.
Motor does not come up to speed
Not applied properly
Consult supplier for proper type.
Voltage too low at motor terminals because of line drop.
Use higher voltage on transformer terminals or reduce load. Check connections.
Check conductors for proper size.
Broken rotor bars or loose rotor.
Look for cracks near the rings. A new rotor may be required as repairs are
usually temporary.
Motor takes too long to accelerate
Open primary circuit
Locate fault with testing device and repair.
Excess loading
Reduce load.
Poor circuit
Check for high resistance.
Defective squirrel cage rotor
Replace with new rotor.
Applied voltage too low
Get power company to increase power tap.
Wrong rotation
Wrong sequence of phases
Reverse connections at motor or at switchboard.
Motor overheats while running under load Overloaded
Reduce load.
Frame or bracket vents may be clogged with dirt and
prevent proper ventilation of motor.
Open vent holes and check for a continuous stream of air from the motor.
Motor may have one phase open
Check to make sure that all leads are well connected.
Unbalanced terminal voltage
Check for faulty leads, connections and transformers.
Motor vibrates after correcting have
been made
Motor misaligned
Realign
Weak support
Strengthen base.
Coupling out of balance
Balance coupling.
Driven equipment unbalanced
Rebalance driven equipment.
Defective ball bearing
Replace bearing.
Bearing not in line
Line properly.
Balancing weights shifted
Rebalance motor.
Polyphase motor running single phase
Check for open circuit.
Excessive end play
Adjust bearing or add washer.
Summary of Contents for Pure Water PWR4021 Series
Page 6: ...6 Figure 2 B Controller Drawing...
Page 7: ...7 B Controller Drawing continued Figure 3...
Page 13: ...13 Figure 6 Wiring Diagram Pictorial Schematic of a Typical ROC 4 System...
Page 15: ...15 Figure 8 Controller Detail Terminal Board TB 3 See Fig 3 for schematic TB24V3...
Page 20: ...20 Figure 11 Controller Programming Menu Navigation...
Page 31: ...31 Notes...