Operation

Once all wiring connections have been completed, the sensor and ProMelt 

mats/cables have been fully installed, and any inspections made as  

required per local code, energize the circuit breaker(s) supplying the panel.

Automatic Operation

This is the recommended mode of operation. The sensor will activate  

the panel, energize the connected ProMelt mats/cables indicated by the 

"Heating On" light on the front of the panel.

Manual Operation

This mode may be used to briefly test the system or temporarily 

override the sensor control to complete melting or drying of a snow 

melted area. If this is required often to help complete the snow melting 

of an area, it is recommended to adjust the sensor control or consult your 

system designers for possible improved automatic sensing and control.
Turn the Timer to the desired time. This overrides the sensor and  

activates the panel, energizing the connected ProMelt mats/cables, 

shown by the "Heating On" light.

Do not manually energize the ProMelt mats/cables with outdoor  

temperatures above 68°F (20ºC) except for a brief test up to 10 

minutes in duration. Damage to the mats/cables or slab/surface 

materials may result.

CP series of controls can be used directly with any ProMelt cable or mat system. Power is connected directly to each contactor in the control.
Each ProMelt system can be used with a wide variety of moisture/precipitation sensors, including the following:

– Slab Mounted:  PM-HSC5

– Pole Mounted:  PM-224 and PM-824
Each sensor option is designed to operate a single system. Use a dedicated sensor and CP Control group for each snow melt zone.

277 VAC

Circuit

Breaker

Panel

Installation Notes:

CABLE TO SENSOR

Class 2 control circuit.

Use 4-conductor shielded, outdoor

rated wire.

See sensor manual for minimum wire

gauge and maximum wire lengths.

120 VAC

Control

Circuit

Branch circuit protection provided by

installer.  Maximum 70A GFEP type.

N

L

N

L

N

L

CP

Contactor

Panel

120 / 208 / 240 VAC

Circuit

Breaker

Panel

N / L1 L2

L1 L2

T2

T1

L2

L1 L2

T2

T1

24

VA

C

Co

m

m

on

PM

CP

Contactor

Panel

C1

C4

BLU BRN YEL

YEL

PM-224

or PM-824

Sensor

Junction

Box

GRN

120

COM

N / L1

208

240

120

COM

208

240

PM-HSC5

Sensor

ProMelt

Transformer Notes:

Connect primary to quick-connect

terminals L1 and L2 on contactor C1.

CAUTION:  Ensure voltage lead

matches supply voltage to C1.

Improper connection may cause

damage.

Branch circuit protection provided by

installer.  Maximum 70A GFEP type.

L1 L2

(Optional)

CP Contactor Panel used as an

"extension" panel

X1

X2

24

VA

C

Co

m

m

on

PM

X1

X2

To optional

additional

CP-Series

panels

rev 071712  Watts Radiant  (800) 276-2419

WIRING

Wire per NEC or CEC and local codes.

Circuit size 125% of load.

Field wiring: Use Copper Conductors

Only, 75C, 20 lb-in (2.3 Nm)

RED BLK ORG

BLU

24

VA

C

Co

m

m

on

PM

X1

X2

T2

T1

L1 L2

T2

T1

C1

C4

Same connections as 120 / 208 / 240 VAC

X1 & X2 are dry contact, N.O.

24

VA

C

24

VA

C

C

O

M

M

O

N

C

O

M

M

O

N

P

M

P

M

X1

X2

Terminal Block Wire Insertion Detail 