Replacing the Media

1.  Shut off the primary water supply going to the 

AquaSolve tank.

2.  Open up a downstream spigot or faucet to release 

pressure in the tank and in the distribution lines 
before and after the system.

3.  Close the inlet and outlet isolation valves immedi-

ately before and after the tank.

4.  Place into By-Pass position, remove bypass clips 

and then disconnect bypass from head.

5.  Using a step ladder and strap wrench, remove 

the threaded head assembly connection (turning 
counter-clockwise) and remove the complete upper 
assembly including the screen attached to the bot-
tom of the head assembly. Rinse these parts in a 
nearby sink or bucket of water. Do not drain the 
tank.

6.  Remove the distributor tube with the bottom strain-

er. Rinse these parts in a nearby sink or bucket of 
water.

7.  Get a 6ft length of 3/4” sch. 40 PVC and a length 

of 1” polyvinyl hose. The length of hose depends 
on the distance to the nearest floor drain. (Both of 
these can be acquired at a local hardware store.)

8.  Insert one end of the pipe inside the hose and put 

the other end of the pipe into the top of the tank 
and down into the media. Put the other end of the 
hose inside a rice bag and put the rice bag on the 
floor drain.

9.  Get a garden hose and put it on the open end of 

the poly hose to fill the hose and pipe with water. 
Air will bubble out of the tank. Once all the air is 
out of the hose and pipe, you can start a siphon to 
remove the media. Put the garden hose in the top 
of the tank and turn it on to keep the tank full of 
water. Push the pipe up and down in the media to 
get it all out. The rice bag will catch the media and 
allow the water to go down the drain.

10.  Try not to be too aggressive when extracting the 

media. You need to take it out in small bites. If you 
let the whole pipe/ hose fill with media it will plug 
up. You need to let slugs of water flush out the pipe 
as you go.

Your AquaSolve media should be replaced every 3 years. Dispose 
of old media and/or container in accordance with local, regional, 
national, and/or international regulations.

NOTICE

11.  When all the old media is removed turn off the  

garden hose and continue to siphon until the tank is 
about half full with water.

12.  Reinstall the distributer tube with bottom strainer 

that was removed in step 6. Center the distributor 
tube in the bottom of the tank, making sure the 
distributor tube is flush with the top of the tank. 
Keeping any and all media from entering the distrib-
utor tube, cap the top open end of the distributor 
tube with plastic sheeting and tape. Test it to make 
sure it will not come off during the media loading 
process. Carefully pour-in a new bag of media that 
specifically meets the replacement requirement 
of the tank. For example, an LM8408-COM sys-
tem requires (x1) LM8408-COM-RM Replacement 
Media.

13.  Inspect the threaded connection on the top of the 

tank to ensure no loose beads of media are stuck 
to the internal threads. If visible, wipe away the 
beads with a damp cloth, then remove the plastic 
sheeting and tape from the top of the distributor 
tube. 

14.  Re-attach the head assembly onto the distributor 

tube and thread the head assembly back onto 
the tank. Fully hand tighten the head to the tank, 
reconnect the bypass to the head and reinstall the 
bypass clips. Insure the Coupling O-rings are not 
pinched.

15.  Turn on the primary water supply and slowly place 

AquaSolve By-Pass Valve into Service position (see 
image on page 6 for reference).

16.  Slowly open the outlet isolation valve and slightly 

open the inlet isolation valve to allow water to flow 
into the system and out of a downstream cold side 
faucet to purge the air from the tank and plumbing 
system.

17.  Once the tank is full of water, 

wait 4 hours for media to  
“hydrate”.

18.  Fully open the inlet isolation  

valve and the system is now  
ready for operation.

Operation & Maintenance Manual

Lync AquaSolve

Summary of Contents for Lync AquaSolve LM8408-COM

Page 1: ...rth TX 76134 817 335 9531 Technical Support 800 433 5654 ext 3 Mon Fri 8 am 5 pm CST Engineered Solutions OMM LM8408_LM8410 COM_EN Important Read this Manual BEFORE using this equipment Failure to rea...

Page 2: ...effec tive alternative technology to a water softener for the prevention of scale due to water hardness Virtually maintenance free no control valve Uses environmentally friendly technology by using no...

Page 3: ...AquaSolve in conjunction with other forms of water treatment 1 AquaSolve must be the last stage in the treatment chain Do not install any filters after AquaSolve or before any devices for which scale...

Page 4: ...pplying excessive flux on the inner surfaces of the pipe and use a low corrosivity water soluble flux listed under the ASTM B813 standard AquaSolve media does not reduce silica scaling While silica te...

Page 5: ...needed for servicing The full weight of the plumbing system must be supported by pipe hangers or other means NOTICE Install Piping Connect the inlet and outlet plumbing according to your preferences a...

Page 6: ...lue structure or appearance of these objects protect remove them or use the outlet hose to drain option 7 Connect the outlet of the AquaSolve system to the cold water supply to the building Install an...

Page 7: ...pe hose fill with media it will plug up You need to let slugs of water flush out the pipe as you go Your AquaSolve media should be replaced every 3 years Dispose of old media and or container in accor...

Page 8: ...F O B nearest factory at no cost excluding freight and local labor charges if any Our obligation under this warranty with respect to the Lync AquaSolve media will be limited to furnishing a replaceme...

Reviews: